140 TP-6694 2/25
6.1.5 Gas Fuel Valve Kit
This section provides the wiring information for an additional gas fuel valve kit required for UL Approval. See the figure below.
Refer to the respective generator set wiring diagrams for additional information and for LP liquid applications.
Figure 75 Gas Fuel Valve Kit Connections
6.1.6 Two-Input/Five-Output Module
Figure 76 Two-Input/Five-Output Module Location
The two-input/five-output module provides a generator set mounted panel with two analog or digital inputs and five digital outputs.
See Figure 78 for circuit board components and electrical connections to the controller.
See Figure 79 for connections of analog inputs.
See the following subsection, Accessory Connections, for terminal identification.
Use a computer with SiteTech software to assign functions to digital outputs. Each input and output corresponds to a controller
connection. Verify that the settings are appropriate for the connected sensor, switch, or equipment.
Refer to IntroductionList of Related Materials for the SiteTech Software Operation Manual part no.
SiteTech analog inputs B1 and B2 and digital outputs B1 through B5 are designated for use on the optional
two-input/five-output module. See Figure 77.
SiteTech I/O Name
Optional I/O Module Connection
Analog Input B1
Analog Input B2
P28 Analog Input VN1/VP1
P28 Analog Input VN2/VP2
Digital Output B1
Digital Output B2
Digital Output B3
Digital Output B4
Digital Output B5
P29 (K1)
P30 (K2)
P31 (K3)
P32 (K4)
P32 (K5)
Figure 77 Input/Output Assignments
Typical for PSI, GM, and Doosan Engines KG80KG125, KG80RKG125R
(KG6208TA Engine) Connections
Note: UL fuel valve is standard on KG40-KG60 (KG6208).
2 input/5 output module