136 TP-6694 2/25
Figure 70 Common Fault Relay Kit and Shunt-Trip Relay Kit Wiring
6.1.4 Four-Input/Fifteen-Output Module
The optional 4-input/15-output module is available for selected models. The 4-input/15-output module is not available with the
2-input/5-output module.
Figure 71 Optional 4-Input/15-Output Module
The optional 4-input/15-output module (see Figure 71 and Figure 72) provides normally open and normally closed contacts to
activate warning devices and other user-provided accessories allowing remote monitoring of the generator set. Connect any
controller fault output to the module. Typically, lamps, audible alarms, or other devices signal the fault conditions.
The 4-input/15-output module is factory-installed and connected to the controller.
A personal computer with SiteTech™ software is required to assign the inputs and outputs. SiteTech™ is available only to
authorized distributors and dealers.
The module has four digital inputs and two analog inputs. There are fourteen programmable relay outputs (K1 – K14) and one
common fault relay output (K15).
When a generator fault condition occurs, the contact kit relay is energized. The relay energization corresponds to the controller
output being activated.
Check the electrical requirements of the user-supplied accessories prior to installation of the input/output module. User-supplied
accessories require their own electrical source and must not exceed the relay contact ratings.