TP-6881 7/15 41Section 3 Controller
SiteTech Group Notes [
Default
Setting
Adjustment
Range *
UnitsParameter
ATS Delays ATS Transfer From Preferred
Delay
s 1--10 3 RXT
ATS Delays ATS T ransfer From Standby
Delay
s 1 -- 600 120 RXT
ATS Delays ATS Source 2 Engine Start
Delay
s 1--10 3 RXT
Modbus Is Modbus Master 0--1 0
Network Configuration DHCP Enabled True or False True OnCue
Plus
Network Configuration Static IP Address 0.0.0.0 --
255.255.255.255
0.0.0.0 OnCue
Plus
Network Configuration Static Subnet Mask 0.0.0.0 --
255.255.255.255
0.0.0.0 OnCue
Plus
Network Configuration Static Default Gateway 0.0.0.0 --
255.255.255.255
0.0.0.0 OnCue
Plus
Network Configuration Static DNS Server 1 0.0.0.0 --
255.255.255.255
0.0.0.0 OnCue
Plus
Network Configuration Static DNS Server 2 0.0.0.0 --
255.255.255.255
0.0.0.0 OnCue
Plus
Network Configuration Server Host Name devices.kohler.com devices.
kohler.com
OnCue
Plus
Network Status IP Address Read Only 0.0.0.0 OnCue
Plus
Network Status Subnet Mask Read Only 0.0.0.0 OnCue
Plus
Network Status Default Gateway Read Only 0.0.0.0 OnCue
Plus
Network Status DNS Server 1 Read Only 0.0.0.0 OnCue
Plus
Network Status DNS Server 2 Read Only 0.0.0.0 OnCue
Plus
Network Status MAC Address Read Only N/A OnCue
Plus
Network Status Connected Server IP Address Read Only 0.0.0.0 OnCue
Plus
Network Status Network Connection
Established
Read Only False OnCue
Plus
Network Status Media Connected Read Only False OnCue
Plus
RBUS Network RBUS Active Read Only False
RBUS Network RBUS Connection Count Read Only 0
RBUS Network RBUS Net Cycle Time ms Read Only 100
RBUS Network RBUS Timeouts Read Only 0
RBUS Network RBUS Errors Read Only 0
* Read Only = Not adjustable
w Load management device (LCM, load shed kit, or RXT w ith c ombined interface/ load management board).
[ Notes indicate applicability to genset or accessories. N/A = Not applicable to the models covered in this manual.
] See TT-1584 for more information about digital inputs and outputs.
Grayed rows are visible in SiteTech but do not apply to all models.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler Power Systems 8RESV and is the answer not in the manual?

Kohler Power Systems 8RESV Specifications

General IconGeneral
BrandKohler
ModelPower Systems 8RESV
CategoryPortable Generator
LanguageEnglish

Related product manuals