The Specification of Power
5. Capacity Tables
5.1 Cooling Capacity
KV24CC-ARF21
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 7.52 7.15 6.79 6.50
SC 5.56 5.51 5.43 5.46
Input 2.10 2.28 2.38 2.46
24/17ºC DB/WB
TC 7.74 7.37 7.01 6.57
SC 5.80 5.75 5.68 5.52
Input 2.23 2.38 2.49 2.61
27/19ºC DB/WB
TC 7.88 7.52 7.30 6.79
SC 5.83 5.79 5.69 5.57
Input 2.28 2.41 2.54 2.66
32/23ºC DB/WB
TC 8.03 7.74 7.59 7.01
SC 6.83 6.73 6.68 6.52
Input 2.38 2.49 2.66 2.76
KV36CC-ARF21
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 11.33 10.78 10.23 9.79
SC 8.38 8.30 8.18 8.22
Input 3.42 3.71 3.88 4.00
24/17ºC DB/WB
TC 11.66 11.11 10.56 9.90
SC 8.75 8.67 8.55 8.32
Input 3.63 3.88 4.04 4.25
27/19ºC DB/WB
TC 11.88 11.33 11.00 10.23
SC 8.79 8.72 8.58 8.39
Input 3.71 3.92 4.13 4.33
32/23ºC DB/WB
TC 12.10 11.66 11.44 10.56
SC 10.29 10.14 10.07 9.82
Input 3.88 4.04 4.33 4.50
KV48CC-ARF21
Cooling Outdoor conditions (DB)
Indoor Conditions (kW) 21ºC 28ºC 35ºC 43ºC
21/15ºC DB/WB
TC 14.42 13.72 13.02 12.46
SC 10.67 10.56 10.42 10.47
Input 3.89 4.22 4.41 4.55
24/17ºC DB/WB
TC 14.84 14.14 13.44 12.60
SC 11.13 11.03 10.89 10.58
Input 4.13 4.41 4.60 4.83
27/19ºC DB/WB
TC 15.12 14.42 14.00 13.02
SC 11.19 11.10 10.92 10.68
Input 4.22 4.45 4.69 4.92
32/23ºC DB/WB
TC 15.40 14.84 14.56 13.44
SC 13.09 12.91 12.81 12.50
Input 4.41 4.60 4.92 5.11
Notes:
TC : Total capacity ; kW
SC: Sensible heat capacity ; kW
Input: Input power; kW
14 Four-way Ceiling Cassette Type