FCU 500, FCU 505 · Edition 02.17 39
Valve proving system
7.1.3 One test volume for system tightness
Z
Z
P
9
5
450
2
2
p
u
/2
PZ
V
p1
V1
V3
p
u
p
z
The tightness control checks the system tightness
of the test volume V
p1
between the central shut-off
valve V1, relief valve V3 and the burner valves. The
opening times of the relief valve V3 and the shut-off
valve V1 are identical.