EasyManua.ls Logo

Kromschroder FCU 500 - Parameters

Kromschroder FCU 500
148 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FCU 500, FCU 505 · Edition 02.17 74
Parameters
12 Parameters
Any changes to parameters will be saved to the parameter chip card.
Name Parameter Value range Description Factory default settings
Emergency stop 10
0
1
2
Off
With safety shut-down
With fault lock-out
2
High gas pressure protection 12
0
1
2
Off
With safety shut-down
With fault lock-out
2
Low gas pressure protection 13
0
1
2
Off
With safety shut-down
With fault lock-out
2
Low air pressure protection 15
0
1
2
Off
With safety shut-down
With fault lock-out
2
Safety time during operation tSB 19 0; 1; 2 Time in seconds 1
Temperature monitoring mode 20
0
1
2
3
Off
STM function
STL function
STM and STL function
FCU..H0 = 0
FCU..H1 = 2
Thermocouple 22
1
2
3
Type K
Type N
Type S
1
Temperature difference limit value 23 10 – 100 Temperature in °C 50
STM limit value (high temperature operation) 24 650 – 1200
STM limit value (high temperature
operation) in °C
750
STL/FSTL limit value (system protection) 25 200 – 1600 STL/FSTL limit value in °C 350
Temperature hysteresis 26 10 – 100 Temperature in °C 50
Pre-purge during high temperature operation 27
0
1
Off
On
1
Fan in the event of fault 29
0
1
Off
On
1
Fan run-up time tGV 30 0 – 6000 Time in seconds 0
Fan ready for operation 31
0
1
2
Off
With safety shut-down
With fault lock-out
2