EasyManuals Logo

KYORITSU 4118A User Manual

KYORITSU 4118A
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
19
6.3
Measurement of Line Impedance and Prospective Short Circuit Current
Line Impedance on single-phase system is the impedance measured
between phase and neutral terminals.
Measurement principle used inside the instrument is exactly the same as at
Fault Loop Impedance measurement, but the measurement is carried out
between L and N terminals.
Breaking current capacity of installed over-current protection devices should
be higher than Prospective Short-Circuit current,
otherwise it is necessary
to change the rated current of involved over-current protection device.
Practical example of line impedance test and prospective short-circuit
current test:
The figure below shows in marked line the Line impedance phase to neutral
for TN system.
Fig.11
 
#
WARNING
(OLD-TT system only)
 
DO NOT PRESS
the "Test button" if the display reads a value of
220V!

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KYORITSU 4118A and is the answer not in the manual?

KYORITSU 4118A Specifications

General IconGeneral
BrandKYORITSU
Model4118A
CategoryTest Equipment
LanguageEnglish

Related product manuals