230
8 CO/O
2
Control
Testing the Correction Effect
Manual adjustment of the correction value can be used to check the switch-off limit of the O
2
monitoring for CO control.
Moving the correction value
1. Open the CO/O
2
curve window.
Fig. 8-21 CO/O
2
data menu
NOTICE
This manual adjustment of the correction value is only possible in the O
2
SETTINGS mode,
’O
2
EI mode active’.
The window ’CO/O
2
curves’ opens.
Fig. 8-22 CO/O
2
curves