70
4 CMS Components
NOTICE
The limits of the technical data must be strictly adhered to.
4.7.3 Functional Description
The UI400 is an HMI for configuration and monitoring.
4.7.4 Pin Assignment
Current draw I
min
: 32 mA – with screen saver, backlight OFF
I
max
: 16 mA – with max. 20 mA/10 V at setpoint outputs.
Function
Housing
Dimensions (H × W × D) [mm] 64 × 112 × 26
Weight [kg] 0,149
Flammability Complies with IACS, E10, test 21
Environmental conditions
Operation Climatic conditions Class 3K5 according to DIN EN 60721-3-3, 5%
95%
Mechanical conditions Class 3M5 according to DIN EN 60721-3-3
Temperature range 20 - +60°C (non-condensing)
Transport Climatic conditions Class 2K3 according to DIN EN 60721-3-2, 95%
Mechanical conditions Class 2M2 according to DIN EN 60721-3-2
Temperature range 40 - +80°C (non-condensing)
Storage Climatic conditions Class 1K3 according to DIN EN 60721-3-1, 5%
95%
Mechanical conditions Class 1M2 according to DIN EN 60721-1
Temperature range 40 - +80°C (non-condensing)
Electrical safety IP rating according to DIN EN 60529 IP54
Fig. 4-37 UI400 terminal assignment
+ RD +24 VDC
- BK GND
H OG CAN H
L BR CAN L

Table of Contents