245
8 CO/O
2
Control
0024 O
2
information O
2
trim is on standby.
0025 O
2
information O
2
trim is deactivated. Firing rate value is outside the control range.
0026 O
2
information O
2
trim is deactivated. Burner is switched off.
0031 O
2
information O
2
trim was switched off via LSB (maintenance/fault in O
2
measure-
ment).
0032 O
2
information Correction value set manually
0034 O
2
information O
2
trim is active.
0046 CO information CO control deactivated. firing rate value is outside the control range.
0048 CO information CO control was deactivated by the SYSTEM BUS (maintenance/fault in
CO/O
2
measurement)
0051 CO information CO curve is active.
0061 O
2
information Curve set change is running.
0062 O
2
information O
2
adjustment is in operation after burner OFF.
0063 O
2
information O
2
trim is inactive in this curve set.
0064 O
2
information O
2
trim is inactive in ADJUST mode.
0065 O
2
information O
2
trim is active.
0066 O
2
information O
2
trim is inactive.
0067 O
2
information O
2
trim is only available in READ mode.
0068 O
2
information O
2
ADJUST mode is active at burner startup.
0069 O
2
fault O
2
setpoint curve is incorrect.
0070 O
2
fault O
2
correction curve is incorrect.
0071 O
2
information O
2
trim – waiting period after curve set change in progress.
0072 O
2
information O
2
trim has been deactivated by parameters.
No. Fault/
information
Comment