263
9 Faults
No. Description D1 D2 Extra
257 Curve set change has failed
A curve set change was not completed until the time-
out expired.
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
00R = 0
Reset
258 Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
R = 0
Power ON Reset
259 Internal fault.
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
0 Fuel train R = 0
Power ON Reset
260 - 278 Internal fault 0 0
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
281 Invalid curve data
Channel number R = 0
Reset
285 Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the
technical support.
– Replace the device
286 Ignition position was left in IGNITION mode.
When using continuous output:
– Check the position-and speed of the channel which
is indicated in D1.
– If position and speed of the channel is OK:
Check EMC influences by ignition transformer. .
– If the speed and position are incorrect:
Check the settings of the frequency inverter
(analogue output)
– Check the smoothness of the control dampers
Fuel train Internal
information
R = 1, 1, 1, 1
Reset
287 Band failure: Setpoint is not in the expected range.
The system detects a band failure. The setpoint
value has been exceeded.
Channel number
(starting at 0)
Setpoint feedback R = 0, 0, 0, 0
Reset

Table of Contents