4 System Operation
4.2 Check Sums - Hours of Operation
4.2.1 Calling the Checksums
Each of the parameter levels is safeguarded by its own checksum. The checksum for each
level and the safety and pre-purge times are displayed here in succession.
Order:
1
st
oil safety time in seconds
2
nd
oil safety time in seconds
1
st
gas safety time in seconds
2
nd
gas safety time in seconds
Pre-purge time in seconds
On the FMS without pilot burner the statement of the 2
nd
safety time contains safety time. The
statement of the 1
st
safety time is then irrelevant.
NOTICE
If the parameter has been changed, the checksum will change, too, if a total reboot has been
proceeded or the duration of 1h has passed.
Switch (1) to SETPOINT FEEDBACK
Press ENTER (3) and keep pressed
the display shows the checksum and the safety
times one after the other.
CRC 16 level 0: adjustable without password
1: adjustable by person commissioning
2: adjustable by the burner manufacturer or the boiler manufacturer
3: adjustable by LAMTEC only
4: adjustable by LAMTEC only