46
4 CMS Components
NOTICE
The limits of the technical data must be strictly adhered to.
Digital output Non-safe, digital output
Relay output, floating
Voltage up to 230 VAC/50 Hz
Rated current: 2 A, cos = 0.2
Fuse protec-
tion:
Resettable/electronic 4.1 A max. (voltage-dependent)
Not resettable 5 A fast-acting
Electrically safe separation from SELV power supply voltage of the
CMS system
Outputs
Environmental conditions
Operation Climatic condition Class 3K5 as per DIN EN 60721-3-3, 5% ... 95 %
Mechanical condition Class 3M5 as per DIN EN 60721-3-3
Temperature range -30...+70 °C (no condensation permitted)
Transport Climatic condition Class 2K4 as per DIN EN 60721-3-2, 95 %
Mechanical condition Class 2M2 as per DIN EN 60721-3-2
Temperature range -40...+80 °C (no condensation permitted)
Storage Climatic condition Class 1K3 as per DIN EN 60721-3-1, 5% ... 95 %
Mechanical condition Class 1M2 as per DIN EN 60721-3-1
Temperature range -40...+80 °C (no condensation permitted)
Electrical safety Protection class according to DIN EN
60529
IP20 (when all terminals are fitted)