16
LA
-
ON
-
RACK
-
V.09
(2U)
13: Battery total AH setting
Interface
Setting
Parameter 2:
Set up the battery total AH of the UPS.
7-999: setting the battery total capacity from 7-999 in AH. Please set the
correct battery total capacity if external battery bank is connected.
14: Charger maximum current setting
Interface
Setting
Parameter 2:
Set up the maximum charger current.
When the UPS is equipped with additional charger, the available setting
options are 2/3/4.
2/3/4: setting the maximum charger current in 2/3/4 Ampere.
When the UPS is long run model, the available setting options are
1/2/4/6/8.
1/2/4/6/8: setting the maximum charger current in 1/2/4/6/8 Ampere.
(Default: 8A)
15: Charger Boost voltage setting
Interface
Setting
Parameter 2:
Set up the charger boost voltage.
225-240: setting the charger boost voltage from 225 to 240(unit:
0.01V/cell). (Default: 236)
16: Charger Float voltage setting
Interface
Sett
ing
Parameter 2:
Set up the charger float voltage.
220-233: setting the charger float voltage from 220 to 233(unit:
0.01V/cell). (Default:228)
00: Exit setting
Interface
Setting
Exit the setting mode.