EasyManua.ls Logo

Lauda Viscotemp 15 G - Page 73

Lauda Viscotemp 15 G
132 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
09/2021 ECO Gold 73 / 134
Cooling thermostats (2)
Calibration thermos.
RE 1225 G
RE 2025 G
RE 1050 G
RE J 1225 G
Operating temperature, ACC *
°C
-25 200
-25 200
-50 200
-25 200
Ambient temperature range
°C
5 40
Temperature stability
K
±0.02
Maximum storage temperature
°C
43
Cooler
Air
Air
Air
Air
Cooling output at
20 °C ambient tempera-
ture,
15 °C cooling water tem-
perature,
3 bar cooling water pressure
and Pump Level 2
20 °C
W
300
300
700
300
10 °C
W
270
260
660
270
0 °C
W
240
230
600
240
-10 °C
W
180
150
520
180
-20 °C
W
90
60
350
90
-25 °C
W
40
30
---
40
-30 °C
W
---
---
190
---
-40 °C
W
---
---
100
---
-50 °C
W
---
---
20
---
Bath volume
liters
9.3 12
14 20
8 10
9.3 12
Bath opening (W x D)
mm
200 x 200
300 x 350
200 x 200
Ø 150
Bath depth
mm
200
160
160
200
Usable depth
mm
180
140
140
180
Height to top edge of bath
mm
443
Overall dimensions (W x D)
mm
250 x 435
350 x 570
280 x 440
250 x 435
Overall height (H)
mm
624
Sound level (1 m)
dB(A)
50
50
52
50
Pump connection
Stainless steel fittings 13 mm (thread M16 x 1)
230 V ±10 %; 50 Hz
Heater rating / power consumption
kW
2.6 / 2.9
2.6 / 2.9
2.6 / 3.3
2.6 / 2.9
Weight
kg
30.4
37.4
35.0
31.5
220 V ±10 %; 60 Hz
Heater rating / power consumption
kW
2.4 / 2.7
2.4 / 2.7
2.4 / 3.1
---
Weight
kg
30.4
37.4
35.0
---
115 V ±10 %; 60 Hz
Heater rating / power consumption
kW
1.3 / 1.6
1.3 / 1.6
1.3 / 1.8
1.3 / 1.6
Weight
kg
30.0
37.0
34.6
31.1
100 V ±10 %; 50/60 Hz
Heater rating / power consumption
kW
1.0 / 1.3
1.0 / 1.3
1.0 / 1.7
---
Weight
kg
30.0
37.0
34.6
---
*ACC range (Active Cooling Control) according to DIN 12876 is the working temperature range for operation with an active refrigerating machine
Technical modifications reserved!