Function settings Code 0008
Sounds the alarm if the set temperature is not reached
within the indicated number of minutes.
Changes the displayed temperature in Degrees F to
match that of a calibration thermometer.
Changes the displayed relative humidity to match that
of a calibration meter.
Limits the range of temperature variance shown in
degrees.
Limits the range of displayed humidity from the set
point. 00 turns this function off.
Function settings Code 0088
Sets the ratio of proportional on time to temperature
difference.
Sets the length of the PID cycle in seconds.
This controls how often the temperature proportional
output will turn on.
Sets the length of time in seconds for each humidity
cycle.
Sets the "on" time in seconds for humidity in each
cycle.
This sets the alarm range for humidity overshoot. It
should be set to 00 to turn it off.
This function is inactive.
Turns alarm output on or off.
Limits the maximum temperature the operator can set.
Sets how long the door can be open before the proofer
turns off. Set to 00 to disable.
Unattended Humidity
Shut-off
Sets how long the proofer can be left unattended (Door
Closed) before the humidity turns off.