Table of Parameters
Pt 0
Vb *1
THR 100
OLM Valid
Sr1 5.0
Sr2 10.0
Sr3 15.0
Sr4 20.0
Sr5 30.0
Sr16 40.0
Sr7 50.0
F--- -
Gr.U -
n Extended Parameters
l Input/Output Parameters
F100 0.0
F101 0.0
F102 2.5
F105 1
F109 0
F110 1
F111 2
F112 3
F113 10
F114 6
F115 7
F116 8
F117 9
F118 5
F130 254
F131 14
F132 10
F137 255
F138 255
F139 0
F167 2.5
F170 60.0
F171 200/400
F172 *1
F173 100
F185 150
l Frequency Parameters
F200 0
F201 0
F202 0.0
F203 100
F204 60.0
F207 1
F210 0
F211 0.0
F212 100
F213 60.0
F240 0.5
F241 0.0
F242 0.0
F250 0.0
F251 50
F252 1.0
F254 0
F256 0.0
F260 5.0
F261 0
F262 0
Title Function Adjustment range
Default setting
Note
V/F control mode
selection 1
Torque boost 1
Motor electronic thermal
protection level 1
Electronic-thermal
protection
characteristic
selection
Preset-speed
operation frequency 1
Preset-speed
operation frequency 2
Preset-speed
operation frequency 3
Preset-speed
operation frequency 4
Preset-speed
operation frequency 5
Preset-speed
operation frequency 6
Preset-speed
operation frequency 7
Extended parameters
Automatic edit function
0:
V/F constant
1: Variable torque
2:
Automatic torque boost control
3: Sensorless Vector control
4: Automatic energy-saving
5: Dynamic automatic energy-
saving (for fans and pumps)
6: Don't choose
0.0 - 30.0 (%)
10 - 100 (%/A) *2
LL - UL (Hz)
LL - UL (Hz)
LL - UL (Hz)
LL - UL (Hz)
LL - UL (Hz)
LL - UL (Hz)
LL - UL (Hz)
-
-
Title Function Adjustment range
Default setting
Note
Frequency priority
selection
VRF input point 1
setting
VRF input point 1
frequency
VRF input point 2
setting
VRF input point 2
frequency
Frequency setting
mode selection 2
VRF2 input point 1
setting
VRF2 input point 1
frequency
VRF2 input point 2
setting
VRF2 input point 2
frequency
Starting frequency setting
Operation starting frequency
Operation starting
frequency hysteresis
DC braking starting
frequency
DC braking current
DC braking time
Motor shaft fixing
control
Auto-stop in case of lower-
limit frequency continuous
operation time
Jog run frequency
Jog run stopping
pattern
Panel jug run mode
0:
fMod
(Switchable to
F207
by the input terminal)
1:
F207 (F207 for output frequencies
equal to or lower than 1.0 Hz)
0-100 (%)
0.0-500.0 (Hz)
0-100 (%)
0.0-500.0 (Hz)
0: Built-in potentiometer
1: VRF
2: VRF2
3: Serial communication
4: Serial communication
5:
External contact point up-down
6: VRF + VRF2 (Override)
0-100 (%)
0.0-500.0 (Hz)
0-100 (%)
0.0-500.0 (Hz)
0.5-10.0 (Hz)
0.0-
FH
(Hz)
0.0-
FH
(Hz)
0.0-
FH
(Hz)
0.0-100 (%/A) *2
0.0- 20.0 (s)
0: Disabled
1: Enabled
0.0: None
0.1~600.0 (s)
F240
~20.0 (Hz)
0: Slowdown stop
1: Coast stop
2: DC braking
0: Disabled
1: Panel jog run mode enabled
Title Function Adjustment range
Default setting
Note
Low-speed signal
output frequency
Speed reach setting
frequency
Speed reach detection band
Priority selection
(both FR-COM, RR-
COM are ON)
Analog/contact input
function selection
(VRF/VRF2 terminal)
Always-active
function selection
Input terminal
selection 1 (FR)
Input terminal
selection 2 (RR)
Input terminal
selection 3 (RST)
Input terminal
selection 4 (DFL)
Input terminal
selection 5 (DFM)
Input terminal
selection 6 (DFH)
Input terminal
selection 7 (VRF2)
0.0 -
FH
(Hz)
0.0 -
FH
(Hz)
0.0 -
FH
(Hz)
0: Reverse
1: Stop
0: VRF - analog input VRF2 -
anolog input
1: VRF - anolog input VRF2 -
contact input (Sink)
2: VRF - analog input VRF2 -
contact input (Source)
3: VRF - contact input (Sink)
VRF2 - contact input (Sink)
4: VRF - contact input (Source)
VRF2 -
contact input (Source)
0-64 (ST)
0-64 (FR)
0-64 (RR)
0-64 (RST)
0-64 (DFL)
0-64 (DFM)
0-64 (DFH)
5-17 (DFHM)
Title Function Adjustment range
Default setting
Note
Input terminal
selection 8 (VRF)
Output terminal
selection 1A (RY-RC)
Output terminal
selection 2A (DRV-OM)
Output terminal
selection 3 (FL)
Output terminal
selection 1B (RY-RC)
Output terminal
selection 2B (DRV-OM)
Output terminal logic
selection (RY-RC,
DRV-OM)
Frequency command
agreement detection range
Base frequency 2
Base frequency
voltage 2
Torque boost quantity 2
Motor electronic-thermal
protection level 2
Stall prevention level 2
5-17 (AD2)
0-255
0-255
0-255
0-255
0-255
0:
F130
and
F137
,
F131
and
F138
1:
F130
or
F137
,
F131
and
F138
2:
F130
and
F137
,
F131
or
F138
3:
F130
or
F137
,
F131
or
F138
0.0 - (Hz)
25.0-500.0 (Hz)
200V class: 50-330 (V)
400V class: 50-660 (V)
0.0-30.0 (%)
10-100 (%/A) *2
10~199 (%/A) *2200: Disabled
Setting
Overload Overload
value
protection stall
0 Valid Invalid
1 Standard Valid Valid
2 motor Invalid Invalid
3 Invalid Valid
4 AF Valid Invalid
5 motor Valid Valid
6 (inverter Invalid Invalid
7 motor) Invalid Valid
*1: Default setting of the parameter differs by each inverter capacity. Refer to "Default settings by Inverter Rating" table on page 19 for actual values.
*2: Unit displayed may be selected by parameter F701 (Unit selection).

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LCI HF-320 a Series and is the answer not in the manual?

LCI HF-320 a Series Specifications

General IconGeneral
BrandLCI
ModelHF-320 a Series
CategoryInverter
LanguageEnglish

Related product manuals