EasyManuals Logo

Leeson 174611 User Manual

Leeson 174611
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
5
Technical data
2 Technical data
2.1 Standards and application conditions
Conformity
CE Low Voltage Directive (73/23/EEC)
Approvals
UL 508C Underwriters Laboratories - Power Conversion Equipment
Input voltage phase imbalance
< 2%
Humidity
< 95% non-condensing
Temperature range
Transport -25 … +70°C
Storage -20 … +70°C
Operation -10 … +55°C (with 2.5%/°C current derating above +40°C)
Installation height
0 … 4000m a.m.s.l.
(with 5%/1000 m current derating above 1000m a.m.s.l.)
Vibration resistance
acceleration resistant up to 1.0g
Earth leakage current
> 3.5 mA to PE
Enclosure
IP 21 / IP 31 / NEMA 1
Protection measures against
short circuit, earth fault, phase loss, over voltage, under voltage, motor
stalling, over temperature, motor overload