4.4.1 Operational Status and Mode(s)
4.4 DISPLAY MESSAGES/ RECORDS
This section lists the event and alarm messages that the UPS might display. The messages
are listed in alphabetical order. This section is listed with each alarm message to help you
troubleshoot problems.
Note: “X” shows that it will be determined by other conditions.
Item Content Displayed
Led
Fault Bypass Battery Inverter
1 Intialized EXTINGUISH EXTINGUISH EXTINGUISH EXTINGUISH
2 Standby Mode EXTINGUISH EXTINGUISH X EXTINGUISH
3 No output EXTINGUISH EXTINGUISH X EXTINGUISH
4 Bypass mode EXTINGUISH LIGHT X EXTINGUISH
5 Utilty Mode EXTINGUISH EXTINGUISH X LIGHT
6 Battery Mode EXTINGUISH EXTINGUISH LIGHT EXTINGUISH
7 Battery Self-diagonostics EXTINGUISH EXTINGUISH LIGHT EXTINGUISH
8 Inverter is starting up EXTINGUISH X X EXTINGUISH
9 EKO mode EXTINGUISH X X X
10 EPO mode LIGHT EXTINGUISH X EXTINGUISH
11 Maintenance Bypass mode EXTINGUISH EXTINGUISH EXTINGUISH EXTINGUISH
12 Fault mode LIGHT X X X