26
ώ Our products are manufactured according to the following EMC international grade
standard and has passed the CE authentication:
EMC standard number Safety standard number
IEC62040-2 IEC62040-1
IEC61000-4-2 GB4943-2005
IEC61000-4-3
IEC61000-4-4
IEC61000-4-5
Type 6 kVA 10 kVA
Capacity 5.4kW 9 kW
AC INPUT
Input Single phase & Ground
Power factor ≥ 0.99(input THDV ≤1%)
Rated voltage 220VAC / 230VAC / 240VAC
Rated frequency 50Hz/60Hz Automatically selected
Voltage range 120~276Vac
Frequency range 45~65Hz
Bypass voltage
range
220Vac maks +25% (+10% ,+15%, 20%, 25%)
230Vac maks:+20% (+10% ,+15%, 20% )
240Vac maks:+15% (+10% ,+15%)
min: default -45%(-20%, -30% , -45%, )
Bypass frequency
range
±1%,±2%,±4%,±5%,±10%
THDI
≤5% (100% liner load, input THDV ≤1%)
≤8% (100% nonlinear load, input THDV ≤1%)
6.2 EMC STANDARD/SAFETY STANDARD
6.3 PRODUCT PERFORMANCE