EasyManua.ls Logo

Lennox 80MGF Series

Lennox 80MGF Series
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 42
PROBLEM 3: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER DOES
NOT ENERGIZE (CONT.).
Condition Possible Cause Corrective Action/Comments
3.3
− Unit operates with a cooling and con-
tinuous fan demand.
Combustion air blower will not start
with a Heating demand.
Diagnostic lights flash the pressure
switch failure code 2 5 minutes after
3.3.1
Miswiring of furnace or improper con-
nections to combustion air blower.
ACTION 1 − Check for correct wiring and loose
connections. Correct wiring and/or replace any
loose connections.
switch failure code 2.5 minutes after
heating demand.
LED#1−Off,
LED#2−Slow Flash
3.3.2
Combustion air blower failure.
ACTION 1 − If there is 120V to combustion air
blower and it does not operate, replace combus-
tion air blower.
PROBLEM 4: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER
ENERGIZES, IGNITOR IS NOT ENERGIZED.
Condition Possible Cause Corrective Action/Comments
4.1
Unit operates with a cooling and
continuous fan demand.
Combustion air blower energizes
with a heating demand
4.1.1
Pressure switch does not close due
to incorrect routing of the pressure
switch tubing.
ACTION 1 Check that the pressure switch tub-
ing is correctly routed. Correctly route pressure
switch tubing.
with a heating demand.
− Diagnostic lights flash the pressure
switch failure code 2.5 minutes after
heating demand.
4.1.2
Pressure switch does not close due
to obstructions in the pressure tub-
ing.
ACTION 1 − Remove any obstructions from the
pressure tubing and/or taps.
LED#1−Off
LED#2−Slow Flash
4.1.3
Pressure switch tubing damaged
ACTION 1 − Check pressure switch tubing for
leaks. Replace any broken tubing.
LED#2 Slow
Flash
4.1.4
Pressure switch does not close due
to a low differential pressure across
the pressure switch.
ACTION 1 − Check the differential pressure
across the pressure switch. This pressure
should exceed the set point listed on the
switch.
ACTION 2 − Check for restricted inlet and ex-
haust vent. Remove all blockage.
ACTION 3 − Check for proper vent sizing and
run length. See installation instructions.
ACTION 4 − Check voltage to combustion air
blower.
4.1.5
Wrong pressure switch installed in
the unit, or pressure switch is out of
calibration.
ACTION 1 − Check that the proper pressure
switch is installed in the unit. Replace pressure
switch if necessary.
4.1.6
Miswiring of furnace or improper con-
nections at pressure switch.
ACTION 1 − Check for correct wiring and loose
connections. Correct wiring and/or replace any
loose connections.
4.1.7
Pressure switch failure.
ACTION 1 If all the above modes of failure have
been checked, the pressure switch may have
failed. Replace pressure switch and determine if
unit will operate.

Related product manuals