EasyManuals Logo

Lennox 80UGH User Manual

Lennox 80UGH
34 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #31 background imageLoading...
Page #31 background image
Page 31
PROBLEM 2: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR INDUCER DOES
NOT ENERGIZE (CONT.).
Condition Possible Cause Corrective Action/Comments
2.3
− Unit operates with a cooling and con-
tinuous fan demand.
Combustion air inducer will not start
with a Heating demand.
Diagnostic lights flash the pressure
switch failure code 2 5 minutes after
2.3.1
Miswiring of furnace or improper con-
nections to combustion air inducer.
ACTION 1 − Check for correct wiring and loose
connections. Correct wiring and/or replace any
loose connections.
switch failure code 2.5 minutes after
heating demand.
LED#1−Off,
LED#2−Slow Flash
2.3.2
Combustion air inducer failure.
ACTION 1 If there is 120V to combustion air in-
ducer and it does not operate, replace combus-
tion air inducer.
PROBLEM 3: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER
ENERGIZES, IGNITOR IS NOT ENERGIZED.
Condition Possible Cause Corrective Action/Comments
3.1
Unit operates with a cooling and
continuous fan demand.
Combustion air inducer energizes
with a heating demand
3.1.1
Pressure switch does not close due
to incorrect routing of the pressure
switch lines.
ACTION 1 Check that the pressure switch lines
are correctly routed. Correctly route pressure
switch lines.
with a heating demand.
− Diagnostic lights flash the pressure
switch failure code 2.5 minutes after
heating demand.
3.1.2
Pressure switch does not close due
to obstructions in the pressure lines.
ACTION 1 − Remove any obstructions from the
the pressure lines and/or taps.
g
LED#1−Off
3.1.3
Pressure switch lines damaged
ACTION 1 − Check pressure switch lines for
leaks. Replace any broken lines.
LED#1 Off
LED#2−Slow Flash
3.1.4
Condensate in pressure switch line.
ACTION 1 Check pressure switch lines for con-
densate. Remove condensate from lines. Check
that the condensate lines are located correctly.
3.1.5
Pressure switchdoes not close due to
a low differential pressure across the
pressure switch.
ACTION 1 − Check the differential pressure
across the pressure switch. This pressure
should exceed the set point listed on the
switch.
ACTION 2 − Check for restricted inlet vent. Re-
move all blockage.
ACTION 3 − Check for proper vent sizing and
run length. See installation instructions.
3.1.6
Wrong pressure switch installed in
the unit, or pressure switch is out of
calibration.
ACTION 1 − Check that the proper pressure
switch is installed in the unit. Replace pressure
switch if necessary.
3.1.7
Miswiring of furnace or improper con-
nections at pressure switch.
ACTION 1 − Check for correct wiring and loose
connections. Correct wiring and/or replace any
loose connections.
3.1.8
Pressure switch failure.
ACTION 1 If all the above modes of failure have
been checked, the pressure switch may have
failed. Replace pressure switch and determine if
unit will operate.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox 80UGH and is the answer not in the manual?

Lennox 80UGH Specifications

General IconGeneral
BrandLennox
Model80UGH
CategoryFurnace
LanguageEnglish

Related product manuals