A95UH1D / 95G1UH 090*C12 Performance (Less Filter)
External
Static
Pressure
in. w.c.
Air Volume / Watts at Various Blower Speeds
High Medium-High Medium-Low Low
cfm Watts cfm Watts cfm Watts cfm Watts
0.00 1630 715 1345 590 1090 475 885 385
0.10 1615 700 1320 580 1070 465 890 380
0.20 1580 675 1305 570 1070 455 890 370
0.30 1525 620 1295 535 1060 435 890 360
0.40 1480 615 1275 515 1055 430 885 350
0.50 1415 565 1220 485 1030 410 860 330
0.60 1350 535 1175 450 1005 390 835 310
0.70 1260 505 1115 415 955 360 785 290
0.80 1190 480 1010 380 880 325 740 285
0.90 1060 435 930 360 795 295 655 250
A95UH1D / 95G1UH 090*C16 Performance (Less Filter)
External
Static
Pressure
in. w.c.
Air Volume / Watts at Various Blower Speeds
High Medium-High Medium-Low Low
cfm Watts cfm Watts cfm Watts cfm Watts
0.00 2140 880 1895 780 1590 645 1350 550
0.10 2110 850 1880 760 1585 635 1360 545
0.20 2060 810 1835 725 1580 620 1360 520
0.30 1990 765 1805 690 1550 585 1365 495
0.40 1925 750 1755 655 1510 545 1330 470
0.50 1830 700 1680 610 1455 525 1285 450
0.60 1720 645 1610 575 1390 480 1230 415
0.70 1600 615 1525 535 1300 465 1165 390
0.80 1455 560 1410 495 1195 430 1035 365
0.90 1300 515 1305 465 1100 390 900 320
A95UH1D / 95G1UH 110*C16 Performance (Less Filter)
External
Static
Pressure
in. w.c.
Air Volume / Watts at Various Blower Speeds
High Medium-High Medium-Low Low
cfm Watts cfm Watts cfm Watts cfm Watts
0.00 2000 910 1675 765 1360 635 1185 525
0.10 1980 895 1650 745 1370 610 1180 505
0.20 1935 855 1600 710 1400 590 1170 485
0.30 1875 830 1560 680 1370 570 1160 490
0.40 1800 785 1490 655 1325 545 1120 455
0.50 1725 720 1400 610 1295 515 1080 435
0.60 1630 685 1335 585 1185 480 1030 410
0.70 1530 665 1290 525 1100 435 940 385
0.80 1410 610 1190 485 985 400 790 365
0.90 1245 560 1000 430 925 380 715 315
NOTE: All air is measured external to unit without lter (lter not furnished - eld provided)