507581-04 Page 23  of  60Issue 2128
Figure 27.  
TYPICAL INTAKE PIPE CONNECTIONS IN UPFLOW DIRECT OR
NON-DIRECT VENT APPLICATIONS
2”
2”
2”
2”
or
AIR
INTAKE
2”
TRANSITION
3”
*2”
Pipe size determined in Table 5
or
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
NOTE: Exhaust pipe and intake pipe must be the same diameter.
Figure 28.  
TYPICAL INTAKE PIPE CONNECTIONS IN HORIZONTAL DIRECT OR NON-DIRECT VENT
APPLICATION (RIGHT-HAND DISCHARGE SHOWN)
2”
2”
2”
2”
or
2”
AIR
INTAKE
TRANSITION
3”
*2”
*2”
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
NOTE: Exhaust pipe and intake pipe must be the same diameter.
Intake Piping 
See Figure 27 through Figure 30
This gas furnace may be installed in either direct vent or non-direct vent applications. In non-direct vent applications, when 
intake air will be drawn into the furnace from the surrounding space, the indoor air quality must be considered and guidelines 
listed in the Combustion, Dilution & Ventilation Air section must be followed.
Follow the next two steps when installing the unit in Direct Vent applications, where combustion air is taken from outdoors 
and  ue  gases  are  discharged  outdoors.  The  provided  air  intake  screen  must  not  be  used  in  direct  vent  applications 
(outdoors).
1.  Use transition solvent cement or a sheet metal screw to secure the intake pipe to the inlet air connector. 
2.  Route  piping  to  outside  of  structure.  Continue  with  installation  following  instructions  given  in  general  guidelines  for 
piping terminations and in intake and exhaust piping terminations for direct vent sections. Refer to Table 5A through 
Table 5C for pipe sizes.