507581-04 Page 55  of  60Issue 2128
6.  If  ame  is  not  detected  after  rst  ignition  trial,  the 
ignition  control  will  repeat  steps  3  and  4  four  more 
times  before  locking  out  the  gas  valve.  The  ignition 
control will then automatically repeat steps 1 through 
6 after 60 minutes. To interrupt the 60 minute period, 
move  thermostat  from  “Heat”  to  “OFF”  then  back  to 
“Heat.” Heating sequence then restarts at step 1.
Gas Pressure Adjustment
Gas Flow (Approximate)
Table 14. 
Gas Meter Clocking Chart
Model
Seconds for One Revolution
Natural LP
1 cu ft 
Dial
2 cu ft 
Dial
1 cu ft 
Dial
2 cu ft 
Dial
-30 120 240 300 600
-45 80 160 200 400
-70 55 110 136 272
-110 33 66 82 164
Natural-1000 btu/cu ft LP-2500 btu/cu ft
Furnace should operate at least 5 minutes before checking 
gas ow. Determine time in seconds for two revolutions of 
gas through  the  meter.  (Two revolutions  assures  a more 
accurate time.) Divide by two and compare to time in Table 
14.  If  manifold  pressure  matches  Table  18  and  rate  is 
incorrect, check gas orices for proper size and restriction. 
Remove temporary gas meter if installed.
NOTE: To  obtain  accurate  reading, shut  off  all  other gas 
appliances connected to meter.
Supply Pressure Measurement
An  inlet  pressure  post  on  the  inlet  side  of  the  gas  valve 
provides  access  to  the  supply  pressure.  See  Figure  67. 
Back  out  the  3/32  Hex  screw  one  turn,  connect  a  piece 
of 5/16” tubing and  connect  to  a  manometer  to measure 
supply pressure.
NOTE: Shut unit  off  and remove  manometer  as  soon  as 
an accurate reading has been obtained. Take care to re-
tighten the 3/32 Hex screw.
Unit Gas
Manifold Pressure in. w.g. Supply Line 
Pressure in. 
w.g. 0 - 10000 ft.
0 - 4500 ft. 4501 - 5500 ft. 5501 - 6500 ft. 6501 - 7500 ft. 7501 - 10000 ft.
Low 
Fire
High 
Fire
Low 
Fire
High 
Fire
Low 
Fire
High 
Fire
Low 
Fire
High 
Fire
Low 
Fire
High 
Fire
Min Max
All 
Sizes
Natural 1.7 3.5 1.6 3.3 1.5 3.2 1.5 3.1 1.7 3.5 4.5 13.0
LP/
Propane
4.5 10.0 4.2 9.4 4.0 9.1 3.9 8.9 4.5 10.0 11.0 13.0
NOTE - A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation 
instruction for the conversion procedure.
Table 18. Manifold and Supply Line Pressure 0 - 10,000 ft.
For  proper  furnace  operation  the  minimum  gas  supply 
pressure is 4.5” w.c and the maximum gas supply pressure 
is  10.5”  w.c  for  natural  gas.  The  minimum  gas  supply 
pressure is 10” w.c. and the maximum gas supply pressure 
is 13” w.c. for LP/propane gas.
Manifold Pressure Measurement
1.  A  manifold  pressure  post  located  on  the  gas  valve 
provides access to the manifold pressure. See Figure 
67. Back out the 3/32 Hex screw one turn, connect a 
piece of 5/16” tubing and connect to a manometer to 
measure supply pressure.
2.  Start unit and allow 5 minutes for unit to reach steady 
state.
3.  While  waiting  for  the  unit  to  stabilize,  observe  the 
ame. Flame should be stable and should not lift from 
burner. Natural gas should burn blue.
4.  After  allowing  unit  to  stabilize  for  5  minutes,  record 
manifold  pressure  and  compare  to  value  given  in 
Table 18.
NOTE: Shut unit  off  and remove  manometer  as  soon  as 
an accurate reading has been obtained. Take care to re-
tighten the 3/32 Hex screw.
Proper Combustion
Furnace should operate minimum 15 minutes with correct 
manifold  pressure  and  gas  ow  rate  before  checking 
combustion.  Take  combustion  sample  beyond  the  ue 
outlet  and  compare  to  the  tables  below.  The  maximum 
carbon monoxide reading should not exceed 100 ppm.
High Altitude Information
NOTE: In  Canada,  certication  for  installations  at 
elevations  over  4500  feet  (1371  m)  is  the  jurisdiction  of 
local authorities.
Units may be installed at altitudes up to 10,000 ft. above 
sea level. See Table 18 for de-rate manifold values. Units 
installed at altitude of 7501 - 10,000 feet require an orice 
change.  Units  installed  at  altitude  of  4501  -  10,000  feet 
(1371 to 3048  m) may require a pressure switch change 
which can be ordered separately. Table 17 lists conversion