Page 102 - IOM / ROOFTOP BALTIC Series - 0704 - E
control interfaces ds50 menu tree
Main Screen Code Description Code Description Code Description Code UNIT Min Factory Max Description
3-Setting 3000 1-General 3100 1-Order 3110 On/Off 3111 On/Off ~ No ~ [On / Off] Unit
Reset Al. 3112 Yes/No ~ No ~ [Reset] Discharges the safety measures
of the unit
Resume 3113 Yes/No ~ No ~ [Override] Cancel any override action
set with the DC50
Test 3114 List 0 0 6 [Quickly / Defrost / Gas 1 Low / Gas 1 High
/ Gas 2 / 24/24 7/7 / Lennox] Test Point Lennox
2-Clock 3120 Hour 3121 h 0 ~ 23 [Clock] Clock setting "Hour"
Minute 3122 m 0 ~ 59 [Clock] Clock setting "Minute"
Day 3123 ~ 1 ~ 31 [Clock] Clock setting "Day"
Month 3124 ~ 1 ~ 12 [Clock] Clock setting "Month"
Year 3125 ~ 2 ~ 99 [Clock] Clock setting "Year"
Win/Sum 3126 Yes/No ~ Yes ~ Automatical control of Winter &
Summer zone or Not
2-Schedule 3200 1-Time 3210 Start Uno 3211 h 0 22 23 [Zone Setting] Starting time
"Hour" for "Unoccupied" zone
Start.Uno 3212 m 0 0 59 [Zone Setting] Starting time
"Minutes" for "Unoccupied" zone
Start z.A 3213 h 0 6 23 [Zone Setting] Starting time "Hour" for "Zone A"
Start.z.A 3214 m 0 0 59 [Zone Setting] Starting time "Minutes" for "Zone A"
Start z.B 3215 h 0 22 23 [Zone Setting] Starting time "Hour" for "Zone B"
Start.z.B 3216 m 0 0 59 [Zone Setting] Starting time "Minutes" for "Zone B"
Start z.C 3217 h 0 22 23 [Zone Setting] Starting time "Hour" for "Zone C"
Start.z.C 3218 m 0 0 59 [Zone Setting] Starting time "Minutes" for "Zone C"
2-Anticipation 3220 Foot 3221 °c -10 10 20 [Anticipation Function] bottom of the slope in °C.
Limit of activation of the function. This allows an
anticipated startup in the morning depending on
the outdoor temperature. Only for the "Zone-A"
Gradient 3222 m/°c 0 0 100 [Anticipation Function] Slope in "Minutes of
anticipation per degrees". This allows an
anticipated startup in the morning depending on
the outdoor temperature. Only for the "Zone-A"