GENERAL DATA
BCK = Cooling only rooftop BHK = Heat pump rooftop BGK = Cooling only with gas fired heatingBDK = Heat pump rooftop with gas fired heating
Table 3.1 SIZE 020 025 030 035
Performance
Nominal Airflow m3/h
Cooling BCK-BGK
Gross Cooling capacity (1) KW
Power input BCK kW
Power Input BGK kW
Full load amps A
Direct start up amps ratio Id / Ia -
COP gross BCK (2) -
COP net global BCK (3) -
COP net global BGK (3) -
Cooling BHK-BDK
Gross Cooling capacity (1) KW
Power input BHK kW
Power Input BDK kW
COP gross BHK (2) -
COP net global BHK (3) -
COP net global BDK (3) -
Heating BHK-BDK
Net heating capacity (1) kW
Power input BHK kW
Power input BDK kW
COP gross BHK (2) -
COP net global BHK (4) -
COP net global BDK (4) -
Heating - gaz fired
Heating capacity kW S / H
Input (small heat / high heat) kW S / H
Thermal efficiency % H
Refrigeration circuit
Nb of Circuits / Compressor type nb / type
Expansion nb / type
Refrigerant charge per circuit Clim / PAC kg
Coils
Indoor Coil :
Face area / nb of rows / Fin per inch m2 / nb / FPI
Outdoor Coil : Face area / nb of rows / Fin per inch m2 / nb / FPI
Ventilation data
Nominal Airflow m3/h
Minimum Airflow m3/h
Maximum Airflow m3/h
External static pressure nom / max Pa
Indoor fan (Centrifugal fan BCK/BHK)
Number / Drive type type
Number of motor nb
Mechanical Power (1) kW
Rotation speed RPM
Indoor fan (Centrifugal fan BGK/BDK S)
Number / Drive type type
Number of motor nb
Mechanical Power gas -S (1) kW
Rotation speed RPM
Outdoor fan (axial)
Number nb
Nominal Airflow m3/h
Motor power kW
Rotation speed RPM
Filter (furnished standard)
Efficiency / filter class / Eurovent type
Nb of filter nb
Filter size mm x mm
Dimension
Length (STD / GAZ) footprint without fresh air hood mm
Height mm
Width footprint without fresh air hood mm
Weight standard unit BCK kg
Weight gas unit BGK kg S
kg H
Acoustic at 100 Pa
Outside sound power on standard unit (1) dB(A)
Indoor blower outlet sound power on standard unit (1) dB(A)
Outside sound power on GAS unit (1) dB(A)
Indoor blower outlet sound power on GAS unit (1) dB(A)
Construction
Casing material
Min Casing thickness cm
Painting type/RAL
Insulation Class type
Cooling mode operating limits
Max. Outdoor temp. at Indoor 27°C DB / 19°C WB °C
Min. Outdoor temp. at Indoor 20°C DB °C
Max. entering Indoor coil temp. at Outdoor 40°C DB °C
Min. entering Indoor coil temp. at Outdoor 35°C DB °C
Heat pump mode operating limits
Min. Outdoor temp. at Indoor 20°C DB °C
Min. entering Indoor coil temp. at Outdoor 7°C DB °C
3600 4500 5400 6300
19,8 24,3 31,2 34,6
8.0 10,9 13,6 16,1
8,2 11,5 14,3 16,8
18,4 23,1 32 37,3
5,7 5,5 3,0 3,3
2,5 2,2 2,3 2,1
2,4 2,2 2,2 2,1
2,3 2,0 2,1 2,0
19,6 23,9 30,9 34,3
8,0 10,9 13,6 16,1
8,2 11,5 14,3 16,8
2,5 2,2 2,3 2,1
2,4 2,1 2,2 2,1
2,3 2,0 2,1 2,0
18,3 23,4 30,2 33,4
6,8 9,1 11,5 12,9
7,0 9,7 12,1 13,5
2,6 2,5 2,6 2,5
2,7 2,6 2,6 2,6
2,6 2,4 2,5 2,5
18.6 / 30,7 18.6 / 30,7 18.2 / 42,8 18.2 / 42,8
20 / 33 20 / 33 20 / 46 20 / 46
93 93 93 93
1 / ZR81 Scroll 1 / ZR11 Scroll 2 / ZR72 Scroll 2 / ZR81 Scroll
1 / TXV 1 / TXV 2 / TXV 2 / TXV
3344
0.63 / 3 / 14 0.63 / 3 / 14 0.87 / 3 / 14 0.87 / 3 / 14
1.1 / 2 / 16 1.1 / 2 / 16 1.5 / 2 / 16 1.5 / 2 / 16
3600 4500 5400 6300
2900 3600 4300 5000
4300 5400 6500 7600
100 / 400 100 / 400 100 / 400 100 / 400
1 / AT 12-9 S 1 / AT 12-9 S 1 / AT 15-11 S 1 / AT 15-11 S
1111
0,75 0,75 0,75 1,10
1430 1430 1320 1320
1 / AT 12-9 S 1 / AT 12-9 S 1 / AT 15-11 S 1 / AT 15-11 S
1111
0,75 1,10 1,10 1,50
865 1009 760 844
2222
7680 7680 11225 11225
0,5 0,5 1,1 1,1
1430 1430 1320 1320
80-85 % / G3 80-85 % / G3 80-85 % / G3 80-85 % / G3
2 2 2 + 2 2 + 2
497x624x45 497x624x45 395x497 + 497x497 395x497 + 497x497
2000 2000 1850 1850
1220 1220 1220 1220
1360 1360 1880 1880
377 428 501 503
419 472 567 572
431 484 586 591
81,0 81,8 80,4 80,6
75,4 79,8 75,7 79,0
81,1 82,1 80,5 80,9
77,9 82,6 77,9 81,3
Aluzinc Aluzinc Aluzinc Aluzinc
0,10 0,10 0,10 0,10
polyester / 9002 polyester / 9002 polyester / 9002 polyester / 9002
M0 M0 M0 M0
45 43 44 42
14 11 11 10
35 35 35 35
20 22 22 21
-10 -7 -10 -8
10 8 8 8
Operating limits
Ventilation dataPhysical data
Performances
Refrigerant
data
(1) All data are at Eurovent condition at 400V/3Ph/50Hz+N.Gross cooling capacity with 35°C DB outdoor, 27°C indoor. Net heating capacity with 7°C DB outdoor, 20° C indoor.
(2)Gross COP =
Gross capacity / unit power input (compressor + con. fan + supply fan + control) (3) Net COP cooling = (Gross cooling capacity - fan motor heat) / unit power input (compressor + con. fan + supply fan +
control) (4)Net COP heating = (Gross heating capacity + fan motor heat) / unit power input (compressor + con. fan + supply fan + contol).