TABLE 6– ELECTRIC HEAT DATA (3 PHASE) – CB29M–41, CB29M–51 CB29M–65
Blower Coil
Model
Electric Heat kW,
Model Number
Number of Volts kW **Btuh
DBlower
Motor
*Minimum Circuit
Model
Number
Model
Number
& Shipping Weight
Steps Input Input Input
Motor
Amps
Ampacity
b 460v–3 ph b
ECB29 10
440 8.4 28,700 1.3 15
10 kW
ECB29
-
10
(28K47)
12 lbs (5 kg)
3 steps
460 9.2 31,400 1.3 16
CB29M 41
12
lb
s.
(5
k
g
)
480 10.0 34,100 1.3 17
CB29M
-
41
ECB29 15
440 12.6 43,000 1.3 22
15 kW
ECB29
-
15
(28K48)
12 lbs (5 kg)
3 steps
460 13.8 47,000 1.3 23
12
lb
s.
(5
k
g
)
480 15.0 51,200 1.3 24
ECB29 10
440 8.4 28,700 1.9 16
10 kW
ECB29
-
10
(28K47)
12 lbs (5 kg)
3 steps
460 9.2 31,400 1.9 17
12
lb
s.
(5
k
g
)
480 10.0 34,100 1.9 17
ECB29 15
440 12.6 43,000 1.9 23
15 kW
ECB29
-
15
(28K48)
12 lbs (5 kg)
3 steps
460 13.8 47,000 1.9 24
CB29M 51
12
lb
s.
(5
k
g
)
480 15.0 51,200 1.9 25
CB29M
-
51
ECB29 20
440 16.8 57,300 1.9 30
20 kW
ECB29
-
20
(28K49)
18 lbs (8 kg)
3 steps
460 18.4 62,700 1.9 31
18
lb
s.
(8
k
g
)
480 20.0 68,200 1.9 32
ECB29 25
440 21.0 71,700 1.9 37
25 kW
ECB29
-
25
(28K50)
18 lbs (8 kg)
3 steps
460 23.0 78,300 1.9 39
18
lb
s.
(8
k
g
)
480 25.0 85,300 1.9 40
ECB29 10
440 8.4 28,700 2.3 17
10 kW
ECB29
-
10
(28K47)
12 lbs (5 kg)
3 steps
460 9.2 31,400 2.3 17
12
lb
s.
(5
k
g
)
480 10.0 34,100 2.3 18
ECB29 15
440 12.6 43,000 2.3 24
15 kW
ECB29
-
15
(28K48)
12 lbs (5 kg)
3 steps
460 13.8 47,000 2.3 25
CB29M 65
12
lb
s.
(5
k
g
)
480 15.0 51,200 2.3 25
CB29M
-
65
ECB29 20
440 16.8 57,300 2.3 30
20 kW
ECB29
-
20
(28K49)
18 lbs (8 kg)
3 steps
460 18.4 62,700 2.3 32
18
lb
s.
(8
k
g
)
480 20.0 68,200 2.3 33
ECB29 25
440 21.0 71,700 2.3 37
25 kW
ECB29
-
25
(28K50)
18 lbs (8 kg)
3 steps
460 23.0 78,300 2.3 39
18
lb
s.
(8
k
g
)
480 25.0 85,300 2.3 40
b {575v–3 ph b
ECB29 20
550 16.8 57,300
{{1.9
24
20 kW
ECB29
-
20
(28K51)
18 lbs (8 kg)
3 steps
575 18.4 62,700
{{1.9
26
{CB29M 51
18
lb
s.
(8
k
g
)
600 20.0 68,200
{{1.9
26
{CB29M
-
51
ECB29 25
550 21.0 71,700
{{1.9
30
25 kW
ECB29
-
25
(28K52)
18 lbs (8 kg)
3 steps
575 23.0 78,300
{{1.9
31
18
lb
s.
(8
k
g
)
600 25.0 85,300
{{1.9
32
ECB29 20
550 16.8 57,300
{{2.3
25
20 kW
ECB29
-
20
(28K51)
18 lbs (8 kg)
3 steps
575 18.4 62,700
{{2.3
26
{CB29M 65
18
lb
s.
(8
k
g
)
600 20.0 68,200
{{2.3
27
{CB29M
-
65
ECB29 25
550 21.0 71,700
{{2.3
30
25 kW
ECB29
-
25
(28K52)
18 lbs (8 kg)
3 steps
575 23.0 78,300
{{2.3
32
18
lb
s.
(8
k
g
)
600 25.0 85,300
{{2.3
33
*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F (75_C).
**Electric heater capacity only — does not include additional blower motor heat capacity.
DMinimum circuit ampacity for blower motor only.
{NOTE ALL 575v ELECTRIC HEATERS ARE USED WITH CB29M-51 & CB29M-65 460v MODEL BLOWER COIL UNITS A STEP-DOWN TRANSFORMER
FOR THE BLOWER COIL UNIT IS FURNISHED WITH ALL 575v ELECTRIC HEATERS.
{{Blower motor is rated at 460v.