Page 31
TABLE 4 CHA16-024/030
Single
Electric
Heater Only
Electric
Electric
Optional Single Point Power Source Boxes
Single
Package
Unit
Model No.
Electric
Heater
Model No.
& Net Weight
No. of
Steps &
Phase
Volts
Input
Heater Only
{Minimum
Circuit
Ampacity
Electric
Heat
kW
Input
Electric
Heat
Btuh
Input
Heater
SubĆFuse
Box
Unit
SubĆFuse
Box
Total Unit &
Electric Heat
{Minimum Circuit
Ampacity
208 23 3.7 12,600 26
ECH16R-5
(34H46)
220 24 4.2 14,300
ECH16R-26/41-
5
27
ECH16R 5
(34H46)
9 lbs. (4 kg)
230 25 4.6 15,700
ECH16R 26/41
5
(34H26)
28
240 26 5.0 17,100 29
208 32 5.3 18,100 35
ECH16R-7
(34H47)
220 34 5.9 20,100
ECH16R-26/65-
7
37
ECH16R 7
(34H47)
5 lbs. (2 kg)
230 35 6.4 21,800
ECH16R 26/65
7
(34H25)
38
CHA16 024
1 ste
p
240 37 7.0 23,900
ECH16-261
40
CHA16-024
1
step
1 phase
208 46 7.5 25,600
ECH16
-
261
(31H10)
48
ECH16R-10
(34H48)
220 48 8.4 28,700
ECH16R-26/65-
10
51
ECH16R 10
(34H48)
5 lbs. (2 kg)
230 50 9.2 34,100
ECH16R 26/65
10
(34H24)
53
240 53 10.0 34,100 55
208 68 11.3 38,600 71
ECH16R-15
(34H48)
220 72 12.6 43,000 75
ECH16R 15
(34H48)
18 lbs. (8 kg)
230 75 13.8 47,100
- - - -
78
240 79 15.0 51,200 81
208 23 3.7 12,600 27
ECH16R-5
(34H46)
220 24 4.2 14,300
ECH16R-26/41-
5
28
ECH16R 5
(34H46)
9 lbs. (4 kg)
230 25 4.6 15,700
ECH16R 26/41
5
(34H26)
29
240 26 5.0 17,100 30
208 32 5.3 18,100 36
ECH16R-7
(34H47)
220 34 5.9 20,100
ECH16R-26/65-
7
ECH16-311
38
ECH16R 7
(34H47)
5 lbs. (2 kg)
230 35 6.4 21,800
ECH16R 26/65
7
(34H25)
ECH16
-
311
(31H11)
39
CHA16 030
1 ste
p
240 37 7.0 23,900 41
CHA16-030
1
step
1 phase
208 46 7.5 25,600 49
ECH16R-10
(34H48)
220 48 8.4 28,700
ECH16R-26/65-
10
52
ECH16R 10
(34H48)
5 lbs. (2 kg)
230 50 9.2 31,400
ECH16R 26/65
10
(34H24)
54
240 53 10.0 34,100 56
208 68 11.3 38,600 72
ECH16R-15
(34H48)
220 72 12.6 43,000 76
ECH16R 15
(34H48)
18 lbs. (8 kg)
230 75 13.8 47,100 79
240 79 15.0 51,200 82
{Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F (75_C).

Related product manuals