19
d01 0 1 1 ag 1 1 1
d03 1 D04 0.1 bar 5.7 5.7 5.7
d04 D03 /12 0.1 bar 35 30 30
d05 10 150 1 60 60 60
d06 0 150 1 0 0 0
d07 1 150 1 8 8 8
d08 10 150 1 40 40 40
d09 0 150 1 10 10 10
F02 0 3 1 int.
1 (EAC 1003-1804) 1 (ANCM 112D-152D) 1 (KSCM 112D-214D)
2 (EAR 1003-1804) 2 (ANHM 112D-152D) 2 (KSHM 112D-214D)
3 (EAC/EAR 251-812) 3 (ANCM/HM 22E-86D) 3 (KSCM/HM 22E-86D)
F05
-40 176 0.1 ºC 28 28 28
/11 /12 0.1 bar
F06
0 50 0.1 ºC 12 12 12
0 30 0.1 bar 6 6 6
F07
0 50 0.1 ºC 10 10 10
0 F5 0.1 bar 2 2 2
F08
-40 176 0.1 ºC 30 30 30
/11 /12 0.1 bar
F09
0 50 0.1 ºC 1 1 1
0 30 0.1 bar 5 5 5
F10
0 50 0.1 ºC 0 0 0
0 F8 0.1 bar 13 13 13
F11 0 120 1 20 20 20
F15 0 3 1 ag 0 0 0
F16 0 50 0.1 bar 5 5 5
F17 0 50 0.1 bar 1 1 1
H06 0 1 1 ag 0 0 0 (KSCM) 1 (KSHM)
H07 0 1 1 ag 1 1 1
H10 1 200 1 ud. 1 1 1
H23 0 1 1 ag 0 0 0
H97 0 999 1 ag
H99 0 999 1 ag
P04 0 3 1 ag 1 1 1
PARAMETERS
PAR.
DESCRIPTION MIN. MAX. VAR. UD.
BY DEFAULT
ECOLEAN AIRCOOLAIR AIRCUBE
Defrost
Defrosting cycle activation.
Start defrosting pressure.
End defrosting pressure.
Min. time to start a defrosting cycle. sec.
Min. duration of a defrosting cycle. sec.
Max. duration of a defrosting cycle. min.
Delay between 2 defrosting cycle requests with in the same circuit.
min.
Defrosting delay between the 2 circuits. min.
Fan
Fan operating mode:
0= Always ON.
1= Depending on compressor (in parallel operating mode).
2= Depending on compressors in ON/OFF control.
3= Depending on compressors in speed control mode.
Temp. value for min. speed cooling.
Pressure value for min. speed cooling. 20 (if F2=3) / 22 (if F2=2) 20 (if F2=3) / 22 (if F2=2) 20 (if F2=3) / 22 (if F2=2)
Differential value for max. speed in cooling mode (temp).
Differential value for max. speed in cooling mode (pres).
Fan shut-down differential in cooling mode (temp).
Fan shut-down differential in cooling mode (pres).
Temperature value for min. speed in heating mode.
Pressure value for min speed cooling. 12 (if F3=3) / 22 (if F3=2) 12 (if F3=3) / 22 (if F3=2) 12 (if F3=3) / 22 (if F3=2)
Differential value for max. speed in heating mode (temp).
Differential value for max. speed in heating mode (pres).
Fan shut-down differential in heating mode (temp).
Fan shut-down differential in heating mode (pres).
Fan starting time.
Activation Low Noise:
0= Deactivate.
1= Activate only in cooling mode.
2= Activate only in heating mode.
3= Activate both in cooling and heating mode.
Differential Low Noise in cooling mode.
Differential Low Noise in heating mode.
Setting
Activate remote change over:
0= Deactivate.
1= Activate.
ON/OFF remoto:
0= Deactivate.
1= Activate.
Serial address.
Activate Modbus.
Expansion board software version.
Software version.
Alarms
Enable part load in high pressure:
0= Capacity control deactivated.
1= Capacity control activated for high pressure.
2= Capacity control activated for low pressure.
3= Capacity control activated for high and low pres.