CLIMATIC
USER MANUAL
CHILLERS
V 2.2

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the Lennox CLIMATIC II and is the answer not in the manual?

Lennox CLIMATIC II Specifications

General IconGeneral
CategoryControl Unit
ModelCLIMATIC II
CompatibilityLennox HVAC Systems
TypeThermostat
Temperature Increment1°F
MountingWall Mount

Summary

CONTROL AND REGULATION

CONTROL OF COMPRESSORS

Manages compressor start-up and stop to avoid anti-short cycle.

CONTROL OF ELECTRONIC EXPANSION VALVE

Controls evaporator filling for efficiency and compressor protection.

OPTIONS

FREE-COOLING

Ensures refrigeration while optimizing free-cooling and limiting consumption.

MANAGEMENT OF UNITS IN PARALLEL

Stages units to adjust cooled fluid temp precisely.

MACHINE FAULTS

TEMPERATURES OF CHILLED WATER OUTSIDE RANGE

Input/output chilled water temp sensor outside authorized range.

INSUFFICIENT FLOW OF CHILLED WATER

Flow switch detects insufficient flow in evaporator for over 2 seconds.

INSUFFICIENT FLOW OF HOT WATER

Flow switch detects insufficient flow in condenser for over 3 seconds.

INCORRECT SEQUENCE OF PHASES

Phase controller tripped, detects inversion or bad phase coupling.

CIRCUITS FAULTS

LOW PRESSURE INSUFFICIENT

Low pressure remains lower than safety limits on circuit n.

EVAPORATOR FREEZING

Evaporation temperature too low, risking freezing.

INSUFFICIENT SUPERHEATING

Superheat level is insufficient for proper operation.

EXPANSION VALVE OPENING INCORRECT

Expansion valve opening not reached during pre-heat phase.

COMPRESSOR FAULTS

COMPRESSOR CUT-OUT SWITCH TRIPPED

Thermomagnetic cut-out switch on compressor tripped.

OIL PRESSURE INSUFFICIENT

Oil pressure insufficient for proper compressor lubrication.

EXCESS HIGH TEMPERATURE

High pressure safety cut-out on compressor tripped.

DISCHARGE TEMPERATURE TOO HIGH

Discharge temperature on compressor stays over 120°C.

INTERNAL PROTECTION TRIPPED

Thermal protection on motor windings tripped.

MISCELLANEOUS FAULTS