-00
26
INSUFFICIENT FLOW OF HOT WATER
Logical variable : DFSEC
Incident codes KP02 : 4
KP07 icon :
Description
The “flow switch” FSC detects insufficient flow insufficient in the condenser for over 3 seconds
Action
F Immediate machine halt.
F The fault is displayed on the screen.
F The remote fault report is delayed for 6 minutes.
Resetting
The machine restarts automatically 20 seconds after the flow of hot water is restored.
Trouble-shooting Solution
Wiring fault on control pump.
Wiring fault on flow controller.
Water filter clogged.
Setting fault on flow controller.
Check pump connection.
Check flow controller connection.
Clean water filter.
Adjust flow controller.