COMPRESSOR CUT-OUT SWITCH TRIPPED
Logical variable : DELECmn
Incident codes KP02 : mn1
KP07 icon :
Description
The thermomagnetic cut-out switch on compressor mn is tripped (ELECmn = 0).
Action
F Immediate halt of compressor mn.
F The fault is displayed on the screen.
F The remote fault report is delayed for 6 minutes.
Resetting
Compressor mn can only be restarted after engagement of the cut-out switch and a manual reset.
Trouble-shooting Solution
Faulty connection or connections too tight.
Cut-out switch wrongly set.
Check connections.
Set the protection in accordance with the rated current
for the compressor.