• 44 • CLIMATIC RT_UNITARY-IOM-1508-E
COMMUNICATION
ALARM 013:
HOT WATER, RISK OF FROSTING
ALARM 014, 015, 016:
GAS BURNER, FAILURE
Description
The status of the hot water signals a risk of frosting on the system.
Action
The alarm is signalling.
Reset
The trip is manually reset.
Possible cause(s)
Problem with wiring.
Remedies
Check the connections.
Description
The gas burner control box has generated a fault and is no longer controlling the fume extractor fan.
Action
Immediate shut down of the gas burner. The alarm is signalling.
Reset
Once the burner control box has been reset for 2 minutes, the alarm 014 or 015 is automatically deleted. Up to 3 trips can occur during
a day and are saved in the alarm history. The two rst trips don’t give the alarm alert, and the alarm counter is reset every day at 11
am. The third trip activates the fault report and must be manually reset
The alarm 016 requests a manual reset.
Possible cause(s)
Problem with wiring connection.
Remedies
Check the gas burner connections.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox CLIMATIC series and is the answer not in the manual?

Lennox CLIMATIC series Specifications

General IconGeneral
ConnectivityWi-Fi
CompatibilityLennox HVAC systems
User InterfaceTouchscreen
Remote AccessYes, via app
Energy ManagementEnergy-saving modes
DisplayColor
Programmability7-day programmable

Related product manuals