EasyManua.ls Logo

Lennox PRODIGY2.0 User Manual

Lennox PRODIGY2.0
167 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
1
PRODIGY
®
2.0
(M3 UNIT CONTROLLER)
APPLICATION GUIDE
507242-03
3/2016
Supersedes 2/2016
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or
loss of life.
Installation and service must be performed by a licensed professional HVAC installer (or equivalent) or service agency.
Table Of Contents
1. Prodigy 2.0 – M3 Unit Controller Description 7...............................................
1.1. Unit Sizes 7.........................................................................
1.2. Add-on Controllers 7..................................................................
1.3. M3 Unit Controller Layout and Connections 8............................................
2. Main Controller Operation 9.................................................................
2.1. Control Type - Thermostat 9...........................................................
2.1.1. Cooling Stages 9............................................................
2.1.2. Heating Stages 10............................................................
2.2. System Mode - Room Sensor Backup Mode Set Points 11..................................
2.2.1. Network Control Panel 11......................................................
2.2.2. Room Sensor Back-Up Modes 11...............................................
2.2.3. Room Sensor Back-Up Mode Set Points 12......................................
2.2.4. L Connection Network Back-Up Mode Requirements 13............................
2.2.5. Heating and Cooling Stages in Room Sensor Mode 13............................
2.2.5.1. Energence LC/LG -036 through -074U (Ultra-High Efficiency Units) 13......
2.2.5.2. Start-Up Delay in Room Sensor Mode 14...............................
2.2.5.3. Blower Operation (Occupied) in Room Sensor Mode 14..................
2.2.5.4. Room Sensor Parameters 14.........................................
3. Unit Component Operation 16................................................................
3.1. Compressor Protection and Delays 16...................................................
3.1.1. Compressor Minimum Run-Time and Off-Delay 16................................
3.1.1.1. All Energence LC/LG Ultra-High Efficiency Units 16......................
3.1.1.2. All Other Energence Models 16........................................
3.1.2. Compressor On Delay 16......................................................
3.1.3. Freeze-stats (S49, S50, S53 and S95) 16........................................
3.1.4. Thermal Protection Switches (S5, S7, S8, S31 and S180) 16.......................
3.1.4.1. Energence Ultra-High Efficiency Units (3- to 6-ton) 17....................
3.1.4.2. Tandem Compressors — Energence Ultra-High Efficiency Units
(7-1/2 to 12-1/2-ton) 17...............................................
3.1.4.3. Tandem Compressors — Energence Ultra-High Efficiency Units
(15- and 20-ton) 17..................................................
3.1.5. High Pressure Switches (S4, S7, S28 and S96) 17................................
3.1.5.1. Energence Ultra-High Efficiency Units (7-1/2 to 12-1/2 ton) 17.............
3.1.5.2. Energence Ultra-High Efficiency Units (15- and 20-ton)
— Tandem Compressors Units 17......................................

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the Lennox PRODIGY2.0 and is the answer not in the manual?

Lennox PRODIGY2.0 Specifications

General IconGeneral
BrandLennox
ModelPRODIGY2.0
CategoryController
LanguageEnglish

Summary

1. Prodigy 2.0 – M3 Unit Controller Description

1.3. M3 Unit Controller Layout and Connections

Details the physical layout and connection ports of the M3 Unit Controller.

2. Main Controller Operation

2.1. Control Type - Thermostat

Describes system operation modes via thermostat, room sensor, or network.

2.1.1. Cooling Stages

Explains the five cooling staging options and configurations.

2.1.2. Heating Stages

Details heating staging options for gas and electric units.

3. Unit Component Operation

3.1. Compressor Protection and Delays

Covers minimum run-time, off-delay, and on-delay for compressors.

3.1.1. Compressor Minimum Run-Time and Off-Delay

Explains compressor run-time and off-delay settings and defaults.

3.1.5. High Pressure Switches (S4, S7, S28 and S96)

Covers high-pressure switch operation and lockout logic.

3.1.6. Low Pressure Switches (S87, S88, S97 and S98)

Explains low-pressure switch function and lockout occurrences.

3.2. Gas Units Burner Protection and Delays

Covers protection mechanisms for gas units, including limits and proof switches.

5. Outdoor Fan Operations

5.3. Low Ambient Conditions (S11, S84, S85 and S94)

Explains fan operation during low ambient conditions.

5.4. Compressor / Fan Configurations

Details compressor and fan configurations by box size.

5.5. Low Ambient Outdoor Fan Control and Cycling

Explains low ambient fan control using pressure switches.

6. Dehumidification Operation

6.1. Supermarket Reheat Operation Settings

Configures Supermarket Reheat operation via thermostat or humidity sensor.

6.2. Humiditrol Dehumidification Operation — (Humiditrol® Reheat)

Details Humiditrol reheat operation based on humidity sensor readings.

7. Increased Dehumidification Operation - Energence Ultra-High Efficiency (3- to 6-ton)

7.2. Increased Dehumidification in Room Sensor Mode

Details increased dehumidification using room sensor and over-cooling limits.

8. Economizer

8.2. Enabling Economizer and Settings

Steps to enable economizer and available configuration types.

8.3. Damper Operation During Free Cooling

Discusses economizer damper operation profiles during free cooling.

8.4. Free Cooling Compressor Lockout Mode and Low Ambient Set Point

Configures compressor lockout and low ambient set points for free cooling.

8.11. Economizer Checkout

Outlines checkout procedures for economizer operation.

9. Demand Control Ventilation (DCV)

9.1. General

Explains using IAQ sensors to control CO2 levels and damper position.

9.2. Default Operation

Details the default IAQ input and damper operation for DCV.

10. Outdoor Air Control (OAC)

10.1. General

Explains OAC as an alternative to DCV for modulating outdoor air damper.

11. Building Pressure Control (BPC)

11.1. General

Describes BPC feature for modulating outdoor air damper to hold constant building pressure.

12. Power Exhaust Operation

12.1. General

Explains M3 unit controller's capability to control power exhaust stages.

13. Supply Air Delivery

13.4. Variable Frequency Drive Control

Explains M3 controller compatibility with VFDs for supply blower control.

13.5. Supply Constant Air Volume (CAV) with Zone Bypass Damper Control

Covers CAV unit bypass damper control for static pressure.

13.5.2. Analog Output Control

Explains analog output control using PID for CAV bypass damper.

14. Discharge Air Control

14.1. Cooling

Discusses auto cycling for discharge air cooling set point maintenance.

14.2. Heating

Covers automatic cycling for discharge air heating set point maintenance.

15. Third-Party Zoning

16. BACnet®

16.1. M3 Unit Controller BACnet® Module

Details the optional BACnet module for MSTP network communication.

21. Advanced Airflow System (Smart Airflow™)

21.1. Calibration

Procedure to determine relationship between motor torque and supply airflow.

21.2. Supply Airflow Measurement and Control

Explains how the system measures and controls supply airflow.

22. Sequence of Operation

22.1. Unit Controller Control Modes

Details various control modes available for the M3 unit controller.

22.1.1. Unit Controller In Room Sensor Mode

Explains controller operation using a room sensor for heating and cooling.

22.1.2. Unit Controller In Thermostat Mode

Describes controller operation using a thermostat for heating and cooling.

22.1.3.2. Demand Control Ventilation (DCV)

Explains DCV for controlling outdoor air based on CO2 levels.

22.2. CAV Units in Single-Zone Applications with a Lennox Room Sensor

Explains controller operation for CAV units with room sensors.

22.2.3. Cooling Demand

Explains compressor staging for maintaining space temperature set point.

22.3. CAV Units in Single-Zone Applications — Wired Thermostat or Third-Party Unit Controller

Covers controller operation for CAV units with wired thermostat or third-party controls.

22.3.1.2. Cooling Demand

Details M3 controller's role in activating compressors for cooling demand.

22.3.2. Discharge Air Temperature Control (4-Heat / 4-Cool)

Explains 4-stage heating/cooling control with thermostats or third-party controllers.

22.3.2.3. Cooling Demand

Covers M3 controller's role in maintaining cooling discharge air temperature set point.

22.3.3. Bypass Zoning Applications (2-Heat / 2-Cool)

Covers controller operation for bypass zoning with 2-stage heating/cooling.

22.3.3.3. Supply Duct Bypass Damper

Describes bypass damper use for supply duct static pressure control.

22.3.4. Bypass Zoning Applications (4-Heat / 4-Cool)

Covers controller operation for bypass zoning with 4-stage heating/cooling.

22.3.4.3. Supply Duct Bypass Damper

Describes bypass damper control for supply duct static pressure.

23. M3 Unit Controller Inputs and Outputs

23.1. General

Overview of M3 unit controller inputs and outputs.

24. M3 User Interface Menu Tree and Display Status Screen

24.1. Menu Tree (Level 1)

Visual representation of the main menu structure.

24.3. System Status Screen

Shows operating mode, alarms, and network status.

24.3.3. Alarm Status Display

Shows how alarms are displayed, including alarming value and event details.

25. Model Number and Configuration ID 1 and 2

25.2. Configuration ID 1

Details the settings for Configuration ID 1 for various features.

25.3. Configuration ID 2

Explains the settings for Configuration ID 2 related to unit features.

26. M3 Unit Controller Parameters

26.2. Unit Controller PC Software

Recommends PC software for adjusting parameters and saving configuration files.

28. Events and Alarms

28.1. Phase - Voltage Detection

Explains the unit's ability to detect frequency, phasing, and voltage levels.

28.2. M3 Unit Controller Alarm and Event Codes

Lists M3 unit controller alarms and event codes with corresponding actions.

Related product manuals