103
24.2.5. Settings
Table 59. Menu Interface (Level 1 - SETTINGS)
NOTE: AVAILABLE MENU OPTIONS ARE DEPENDENT ON HARDWARE CONFIGURATION. USE THE ADJUST AND SET VALUES ARROWS
TO SCROLL UP OR DOWN FOR SELECTION OPTIONS.
Level 2 Level 3 Level 4 Level 5 Level 6 Level 7
CONTROL
CONTROL TYPE =
NETWORK OR
WIRED
THERMOSTAT
WIRED THERMOSTAT
NETWORK >
BACNET
BACNET MAC ADDRESS = X
BACNET BAUD RATE = 9.6, 19.2, 38.4 OR 76.8 K
CONTROL MODE = ROOM SENSOR OR NETWORK THERMOSTAT
CONTROL MODE =
MONITOR
CONTROL MODE =
ROOM SENSOR OR
NETWORK
THERMOSTAT
NETWORK SENSOR C02 = YES OR NO
NETWORK SENSOR RELATIVE HUMIDITY = YES
OR NO
NETWORK SENSOR TEMPERATURE = YES OR
NO
ROOM SENSOR OCC BLOWER MODE = AUTO -
CYCLES OR ON - CONTINUOUS 1, 2, 3
BACKUP MODE = NONE, ROOM SENSOR, RE
TURN AIR BACKUP OR THERMOSTAT
RAT OR ROOM
BACKUP SETPOINTS
OCCUPIED HEAT = XX.X F
BACKUP SETPOINTS
UNOCCUPIED HEAT =
XX.X F
BACKUP SETPOINTS
OCCUPIED COOL = XX.X F
BACKUP SETPOINTS
UNOCCUPIED COOL =
XX.X F
NETWORK >
L-CONNECTION
LCONN ADDRESS = X
CONTROL MODE = MONITOR
CONTROL MODE =
ROOM SENSOR OR
NETWORK
THERMOSTAT
NETWORK SENSOR C02 = YES OR NO
NETWORK SENSOR RELATIVE HUMIDITY = YES
OR NO
NETWORK SENSOR TEMPERATURE = YES OR
NO
ROOM SENSOR OCC BLOWER MODE=ON-CON
TINUOUS 1, 2, 3 OR AUTO CYCLES
CONTROL MODE =
ROOM SENSOR OR
NETWORK
THERMOSTAT
BACKUP MODE = NONE, ROOM SENSOR, RE
TURN AIR BACKUP OR THERMOSTAT
RAT OR ROOM
BACKUP SETPOINTS
OCCUPIED HEAT = XX.X F
BACKUP SETPOINTS
UNOCCUPIED HEAT =
XX.X F
BACKUP SETPOINTS
OCCUPIED COOL = XX.X F
BACKUP SETPOINTS
UNOCCUPIED COOL =
XX.X F