Lennox PRODIGY2.0 - 25.2. Configuration ID 1

Lennox PRODIGY2.0
167 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
111
25.2. Configuration ID 1
CONFIGURATION ID 1
Humiditrol [1]
Not Installed = N
Humiditrol Installed = H
Unconfigured = U
Economizer [2]
Not Installed = N
Motorized Outdoor Air
Damper Only = M
Economizer - Temperature = T
Economizer Global = G
Economizer - Single
Enthalpy = S
Economizer - Dual Enthalpy = D
Unconfigured = U
Power Exhaust [3]
Not Installed = N
Single-Stage = S
Dual-Stage = D
Variable Speed Drive = V
Unconfigured = U
Power Exhaust Control [4]
Not Installed = N
Damper Position = A
S37 Pressure Switch = B
A34 Pressure Sensor = C
A34 Pressure Sensor with
Enable Switch = D
S27 and S39 Pressure
Switch = E
[5] Network Module
N = Not Installed
B = BACnet
L = LonTalk (Lennox)
[6] Blower Variable
Frequency Drive Bypass
N = Not Installed
A = Automatic Bypass
M = Manual Bypass
U = Electronic Bypass Field
Un-configured
[7] Advanced Air Flow
Control System
N = Not Installed
S = Installed with Standard
Economizer
L = Installed with High Performance
Economizer
U = Unconfigured
[8] Outdoor Air CFM Control
N = Not applicable (for future use)
L = Outdoor Air Control Installed
with A24 Sensor set for low range.
M = Outdoor Air Control Installed
with A24 Sensor set for medium
range.
H = Outdoor Air Control Installed
with A24 Sensor set for high
range.
IMPORTANT: Always refer to the white sticker titled ORIGINAL FACTORY UNIT CONFIGURATION located inside the control box area.
NOTE: The M3 unit controller will display applicable alarm(s) if any positions is left unconfigured (U).
1 2 3 4 5 6 7 8
Figure 35. Configuration ID 1