Table 58. Menu Interface (Level 1 - SERVICE)
NOTE: AVAILABLE MENU OPTIONS ARE DEPENDENT ON HARDWARE CONFIGURATION.
TEST MENU SECTION: EACH MAJOR COMPONENT OF THE M3 UNIT CONTROLLER WILL INCLUDE A TEST MODE TO VERIFY CRITICAL
COMPONENT AND SYSTEM PERFORMANCE. ALL BLOWER TESTING WILL REMAIN ACTIVE FOR TWO HOURS UNLESS TERMINATED BY
THE USER.
Level 1
WHEN SELECTED (PRESS BACK TO RETURN TO
THE PREVIOUS MENU)
Use the Adjust and set values
arrows to scroll up or down for
selection options.
Level 3Level 2
SERVICE
TEST OUTPUTS SERVICE RELAY SERVICE RELAY ON
REPLACE
FILTER RESET RUNTIME? = NO OR YES
BELT
(only available based
on model number)
RESET RUNTIME? = NO OR YES
UV LAMP
RESET RUNTIME? = NO OR YES OR NOT APPLICABLE EQUIPMENT NOT
PRESENT
FANS (1 through 6)
RESET RUNTIME? = NO OR YES OR NOT APPLICABLE EQUIPMENT NOT
PRESENT
BLOWER RESET RUNTIME? = NO OR YES
COMPRESSOR (1
through 4)
RESET RUNTIME? = NO OR YES OR NOT APPLICABLE EQUIPMENT NOT
PRESENT
REPORT
USB SERVICE
REPORT
USB SERVICE REPORT = DEFAULT NAME IS THE SERIAL NUMBER IF SET. OTH
ERWISE IT WILL BE 123456789. CAN BE RENAMED BY USER. MAXIMUM 18
CHARACTERS.
USB ADV AIRFLOW
RPT
USB ADVANCED AIRFLOW
REPORT = START USB RE
PORT OR USB REPORT
DONE.
START USB REPORT = SAF_RPT (DEFAULT) AND
CAN BE RENAMED BY USER. MAXIMUM 18
CHARACTERS.
SAVE USER
PROFILE
SAVE USER PROFILE = YES OR NO
LOAD USER
PROFILE
LOAD USER PROFILE = YES OR NO
USB PROFILE SAVE
USB PROFILE SAVE = 1234 UNLESS CATALOG NUMBER IS SET. DEFAULT IS
CATALOG NUMBER. CAN BE RENAMED BY USER. MAXIMUM 18 CHARACTERS.
USB PROFILE LOAD
USB PROFILE LOAD =
1234XXXXXXXXXXX (USER
ASSIGNED NAME AS SPE
CIFICED. TYPICALLY CATA
LOG NUMBER.
WILL LOAD PREVIOUSLY SAVED USB PROFILE.
LOAD FACTORY
PROF
LOAD FACTORY PROF = YES OR NO
LOG SERVICE
EVENT
LOG SERVICE EVENT = YES OR NO
SOFTWARE
UPDATE
SOFTWARE
UPDATE
SOFTWARE UPDATE (EITHER
THE UPDATE WILL BE SUC
CESSFUL OR THE FOLLOW
ING MESSAGES WILL AP
PEAR. SW UPDATE FAILED
OR SW UPDATE FILE NOT
FOUND.
NOTE: IF USB FLASH DRIVE IS NOT INSTALLED
OR THE M3 UNIT CONTROLLER CANNOT READ
THE FLASH MEDIA, A MESSAGE WILL APPEAR
“NOT APPLICABLE EQUIPMENT NOT PRESENT.”
OFFLINE
CLEAR DELAYS CLEAR DELAYS = YES OR NO.
RESET
CONTROLLER
RESET CONTROLLER = YES
OR NO.
NOTE: THIS REBOOTS THE M3 CONTROLLER.
NO CONFIGURATION SETTINGS ARE CHANGED.
CONTROLLER
LOCKOUT
CONTROLLER LOCKOUT = YES OR NO.
NOTE: PARAMETERS AVAILABLE ARE DEPENDENT ON MODEL NUMBER AND CONFIGURATION ID 1 AND 2 SETTINGS.