• 50 • CLIMATIC RT_UNITARY-IOM-1508-E
COMMUNICATION
ALARM 056, 059, 080, 081, 082, 083, 084, 085, 086, 087, 088, 089, 141, 142, 143, 144, 241, 242, 243, 244, 341, 342,
343, 344:
PROBE & SENSOR, FAULTY
Description
The temperature probe or pressure sensor measured by the CLIMATIC or other expansion boards is incorrect. The device may
be disconnected or in short circuit for 5s.
Alarm 056: the recovery air ow sensor value is incorrect,
Alarm 059: the outlet recovery air temperature probe value is incorrect,
Alarm 080: the supply air ow sensor value is incorrect,
Alarm 081: the room air temperature probe value is incorrect,
Alarm 082: the room air humidity sensor value is incorrect,
Alarm 083: the outside air temperature probe value is incorrect,
Alarm 084: the outside air humidity sensor value is incorrect,
Alarm 085: the supply air temperature probe value is incorrect,
Alarm 086: the inlet water condenser temperature probe value is incorrect,
Alarm 087: the outlet water condenser temperature probe value is incorrect,
Alarm 088: the return air temperature probe value is incorrect,
Alarm 089: the air quality sensor value is incorrect,
Alarm 141, 241, 341: the high pressure sensor value on circuit 1, 2 or 3 is incorrect,
Alarm 142, 242, 342: the low pressure sensor value on circuit 1, 2 or 3 is incorrect,
Alarm 143, 243, 343: the liquid temperature probe value on circuit 1, 2 or 3 is incorrect,
Alarm 144, 244, 344: the suction temperature probe value on circuit 1, 2 or 3 is incorrect,
Action
Alarm 056: immediate shut down of the recovery module. The alarm is signaling,
Alarm 059: immediate shut down of the recovery module. The alarm is signaling,
Alarm 080: immediate shut down of the complete unit. The blower still works, The alarm is signaling,
Alarm 081: immediate shut down of the complete unit. The blower still works, The alarm is signaling,
Alarm 082: immediate shut down of the complete unit. The blower still works, The alarm is signaling,
Alarm 083: immediate shut down of the complete unit. The blower still works, The alarm is signaling,
Alarm 084: immediate shut down of the complete unit. The blower still works, The alarm is signaling,
Alarm 085: immediate shut down of the complete unit. The blower still works, The alarm is signaling,
Alarm 086: immediate shut down of all circuit. The alarm is signaling,
Alarm 087: immediate shut down of all circuit. The alarm is signaling,
Alarm 089: don’t stop the unit. The alarm is signaling,
Alarm 141, 241, 341: immediate shut down of the circuit 1, 2 or 3. The alarm is signaling,
Alarm 142, 242, 342: immediate shut down of the circuit 1, 2 or 3. The alarm is signaling,
Alarm 143, 243, 343: immediate shut down of the circuit 1, 2 or 3. The alarm is signaling,
Alarm 144, 244, 344: immediate shut down of the circuit 1, 2 or 3. The alarm is signaling,
Reset
Once the data read is coherent for 2 minutes, the alarm is automatically deleted.
Possible cause(s)
Problem with wiring connection,
Probe or sensor damaged.
Remedies
Check the wiring connections,
Replace the probe or sensor.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox CLIMATIC series and is the answer not in the manual?

Lennox CLIMATIC series Specifications

General IconGeneral
ConnectivityWi-Fi
CompatibilityLennox HVAC systems
User InterfaceTouchscreen
Remote AccessYes, via app
Energy ManagementEnergy-saving modes
DisplayColor
Programmability7-day programmable

Related product manuals