• 53 •CLIMATIC RT_UNITARY-IOM-1508-E
COMMUNICATION
ALARM 110, 210, 310:
LEAK REFRIGERANT, DETECTION
Description
The CLIMATIC has detected a risk of leakage of the refrigerant circuit.
Action
The alarm is signalling.
Reset
The alarm is manually reset.
Possible cause(s)
Problem of refrigerant capacity.
Remedies
Check the frigori c system operation
ALARM 114, 214, 314:
COMPRESSOR, ELECTRICAL FAILURE
Description
The thermal magnetic circuit breaker protection or the thermal motor protection of the compressor has tripped.
Alarm n14: thermal magnetic circuit breaker on circuit n,
Action
Immediate shut down of the complete circuit. The alarm is signalling.
Reset
Once the circuit has been stopped for 30 minutes, the alarm is automatically deleted. Up to 3 trips can occur during a day and are
saved in the alarm history. The two rst trips don’t give the alarm alert, and the alarm counter is reset every day at 11 am. The third
trip activates the fault report and must be manually reset.
Possible cause(s)
Problem with wiring connection,
Coil condenser dirty,
Fan condenser not operating.
Remedies
Check the wiring connection,
Clean the coil condenser,
Check the fan operating.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox CLIMATIC series and is the answer not in the manual?

Lennox CLIMATIC series Specifications

General IconGeneral
ConnectivityWi-Fi
CompatibilityLennox HVAC systems
User InterfaceTouchscreen
Remote AccessYes, via app
Energy ManagementEnergy-saving modes
DisplayColor
Programmability7-day programmable

Related product manuals