EasyManua.ls Logo

Lennox EL195UHNE Series

Lennox EL195UHNE Series
53 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 40
Manifold and Signal Pressure Measurement
To correctly measure manifold and signal pressure, follow
the steps below:
1 - Turn o󰀨 the electrical power and gas supply to the
furnace.
2 - Remove the threaded plug from the outlet side of
the gas valve and install a eld-provided barbed
tting. Connect measuring device positive “+” to
barbed tting to measure manifold pressure. See
gure 52 for manifold location.
3 - Install hoses and meter as shown in gure 56 for
signal pressure measurement.
4 - After allowing unit to stabilize for 8 minutes, record
manifold pressure and compare to value in table 18.
If manifold pressure is within range, rate check is
complete move to step 6. If manifold pressure is not
within range continue. Valve is not adjustable. Do
not adjust manifold pressure.
5 - Record signal pressure and compare to value in table
18. If signal pressure is within range continue. If the
signal is not within range go to “Troubleshooting”.
6 - Shut o󰀨 unit and remove manometer and signal
meter after accurate readings has been obtained.
7 - Restart unit and check for gas leaks. Seal any leaks
found.
If the unit has diculty igniting or ignites with loud
resonance the air orice must be checked and re-
placed if necessary.
TABLE 18
Manifold and Signal Pressure (inches w.c.)
Altitude Unit
Natural
Manifold
Propane
Manifold
Signal
0 - 4500 ft
-040
3.2 - 3.8
n/a 0.80-0.93
-060
3.6
0.69-0.93
-080 0.73-0.93
-100 n/a 0.75-0.82
4501 - 7500 ft
-040 3.2 n/a 0.78-0.82
-060 2.3 2.5 0.55-0.62
-080 2.4 2.8 0.58-0.62
-100 2.3 n/a
0.55-0.60
Air Orice Replacement
Do not replace the air orice until the problem has been
determined. If the unit has di󰀩culty igniting the orice is
oversized and brings in too much air. If the unit ignites
but with loud resonance the orice is too small and needs
more air. The air orice is located inside the gray coupling
between the clamps. Figure 55 show corresponding steps
with the steps below.
1 - Turn o󰀨 the electrical power and gas supply to the
furnace.
2 - Remove the black air pressure tube on the air intake
coupling.
3 - Use a 5/16” nut driver to loosen the clamps on the
gray coupling.
4 - Remove the two screws attaching the air intake
coupling to the furnace cabinet.
5 - Remove the air intake coupling. If the air intake
coupling is still too di󰀩cult to remove, then remove
the two screws from the right side of the top cap
and one from the far right side of the blower deck
that attaches to the cabinet. See gure 54. Carefully
pull cabinet side away from air intake coupling, then
remove the air intake coupling. Note: Be careful not
to bend the cabinet side.
6 - Remove the air orice. Check the “Part” number
stamped on the air orice. See table 19. If the part
number is incorrect, then replace it with the proper
air orice. Repeat manifold check. If air orice
is correct diameter, then it must be replaced to
resolve ignition or resonance issue. See table 19
for replacement.
7 - Reinstall the air orice on the left side of the coupling
and push rmly into place.
8 - Reinstall air intake coupling making sure it is fully
seated in the gray coupling. Re-install the two
screws attaching the air intake coupling to the
furnace cabinet. Tighten clamps to secure the
coupling. Re-install the two screws on the right side
of the top cap and the one screw that attaches the
blower deck to the cabinet.
9 - Reconnect the black air pressure tube.
10 - Repeat manifold and signal pressure check. If
unit ignites and manifold and signal pressure are
correct, move on to combustion check. If unit still
does not ignite or ignites with loud resonance go to
Troubleshooting gure 57.

Other manuals for Lennox EL195UHNE Series

Related product manuals