EasyManua.ls Logo

Lennox G43UF SERIES

Lennox G43UF SERIES
55 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 54
PROBLEM 5: BURNERS LIGHT WITH HEATING DEMAND BUT UNIT SHUTS DOWN
PREMATURELY (CONT.)
Condition Possible Cause Corrective Action/Comments
5.3
− Combustion air inducer energizes
with a heating demand.
− Burners light.
− Roll−out switch trips during the
heating demand.
− Diagnostic lights flash roll−out fail-
ure.
5.3.1
Unit is firing above 100% of the
nameplate input.
ACTION 1 − Check that the manifold pressure
matches value listed on nameplate. See installa-
tion instructions for proper procedure.
ACTION 2 − Verify that the installed orifice size
match the size listed on the nameplate or installa-
tion instructions.
ACTION 3Check gas valve sensing hose to in-
sure no leaks are present.
ACTION 4 − Check the input rate to verify rate
matches value listed on nameplate.
ure.
LED#1−On
LED#2−Slow Flash
5.3.2
Gas orifices leak at the manifold con-
nection.
ACTION 1 − Tighten orifice until leak is sealed.
NOTE: Be careful not to strip orifice threads.
ACTION 2 − Check for gas leakage at the
threaded orifice connection. Use approved meth-
od for leak detection (see unit instructions).
5.3.3
Air leakage at the connections be-
tween the primary heat exchanger,
secondary heat exchanger, and com-
bustion air blower.
ACTION 1 − Check for air leakage at all joints in
the heat exchanger assembly. Condition will
cause high CO2 with high CO.
ACTION 2 − Seal leakage if possible, replace
heat exchanger if necessary, tag and return heat
exchanger to proper Lennox personnel.
5.3.4
Insufficient flow through the heat ex-
changer caused by a sooted or re-
stricted heat exchanger.
ACTION 1 − Check for sooting deposits or other
restrictions in the heat exchanger assembly.
Clean assembly as outlined in instruction manu-
al.
ACTION 2 − Check for proper combustion.
5.3.5
Burners are not properly located in
the burner box.
ACTION 1 Check that the burners are firing into
the center of the heat exchanger openings. Cor-
rect the location of the burners if necessary.
5.4
Combustion air inducer energizes
with a heating demand.
− Burners light roughly and the unit
fails to stay lit.
Di ti li ht fl h t h d
5.4.1
Recirculation of flue gases. This con-
dition causes rough ignitions and op-
eration. Problem is characterized by
nuisance flame failures.
ACTION 1 − Check for proper flow of exhaust
gases away from intake vent. Remove any ob-
stacles in front of the intake and exhaust vent
which would cause recirculation.
ACTION 2 Check for correct intake and exhaust
vent installation. See instructions
− Diagnostic lights flash watchguard
flame failure.
5.4.2
Improper burner cross−overs
ACTION 1 − Remove burner and inspect the
cross−overs for burrs, or any restriction or if
crossover is warped. Remove restriction or re-
place burners.
LED#1−Alternating Slow Flash
LED#2−Alternating Slow Flash
5.4.3
Prove Switch opens 5 times during a
single demand
ACTION 1Inspect vent pipe installation and for
any restriction. Remove restriction.
ACTION 2 − Check prove switch reliability.

Table of Contents

Other manuals for Lennox G43UF SERIES

Related product manuals