EasyManua.ls Logo

Lennox G61MPV Series

Lennox G61MPV Series
67 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
G61MPV UNIT
SUPPLY AIR PLENUM
PROPERLY
SIZED FLOOR _X_,J_€ "
OPENING I\\_ L_ ADDITIVE BASE
FIGURE 13
Installation on Cooling Cabinet
1 - Refer to reverse-flow coil installation instructions for
correctly sized opening in floor and installation of cabi-
net,
2 - When cooling cabinet is in place, set and secure the
furnace according to the instructions that are provided
with the cooling coil, Secure the furnace to the cabinet,
3 - Seal the cabinet and check for air leaks,
Return Air Opening -- Downflow Units
Return air may be brought in only through the top opening
of a furnace installed in the downflow position.The follow-
ing steps should be taken when installing plenum:
1 - Bottom edge of plenum should be flanged with a
hemmed edge (See figure 14 or 15),
2 - Sealing strips should be used to ensure an airtight seal
between the cabinet and the plenum.
3 - In all cases, plenum should be secured to top of fur-
nace using sheet metal screws,
4 - Make certain that an adequate seal is made,
PLENUM ----__ I""11"_
(Field Provided) _ SECURE FROM
_UTSIDE CABINET
/ v II .. CABINET
SEALING STRIP _ IIJ SIDE PANEL
(Field Provided) ...... II
Side View II
FIGURE 14
PLENUM _
(Field Provided)
SECURE FROM
INSIDE CABINET
Side View
SEALING STRIP
Field Provided)
CABINET
SIDE PANEL
FIGURE 15
Horizontal Applications
The G61MPV furnace can be installed in horizontal ap-
plications with either right- or left-hand air discharge,
Refer to figure 16 for clearances in horizontal applications,
================================================================================================
Horizontal Application
Installation Clearances
Right-Hand Discharge
Top
Left End Right End
Left-Hand Discharge
Top
Left End Right End
Bottom (Floor)**
i........................................i.............................................]
Front* i O
'.................... ....................t..............................................
I
Ends ! O
Floor i O:_
*Front clearance in alcove installation must be 24 in. (610 ram).
Maintain a minimum of 24 in. (610 ram) for front service access.
**A 5-I12" service clearance must be maintained below the unit to
provide for servicing of the condensate trap.
i :]:For installations on a combustible floor, do not install the fur-
l nace directly on carpeting, tile or other combustible materials oth-
Ler.t.h.an. w.°° d.f.I.°.°ri.n,g: ...............................................................
FIGURE 16
Page 13

Related product manuals