Page 29
OFF
OFF
100% CFM
100% CFM
DEMAND
45 SEC.
Ramping Option D
S Motor runs at 100% until demand is satisfied.
S Once demand is met, motor ramps down to stop.
OFFOFF
100% CFM
COOLING
 DEMAND
Switches 7 and 8 −− Heating Mode Blower Speed −−
Switches  7 and 8 are used to select heating mode blower
motor speed. The unit is shipped from the factory with the
dip switches positioned for medium low (2) speed indoor
blower motor operation during the heating  mode. The table
below provides the heating mode blower speeds that will
result from different switch settings. Refer to tables 14
through NO TAG for corresponding L/s values.
TABLE 13
Heating Mode Blower Speeds
Speed
Switch 7 Switch 8
1 − Low On On
2 − Medium Low
(Factory)
Off On
3 − Medium High On Off
4 − High Off Off
TABLE 14
G61MPVT−36B−070 BLOWER MOTOR PERFORMANCE (LESS FILTER)
0.0" to 0.8" w.g. (0 through 200 Pa) External Static Pressure Range
Factory Settings: Heating Speed − 2; Cooling Speed − 4; Speed Adjust − NORM
ADJUST"
Switch
Positions
Speed Switch Positions
Second Stage HEAT" Speed Second Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
895 420 1025 485 1290 610 1340 630 1015 480 1190 560 1280 605 1395 660
NORM 820 385 940 445 1155 545 1210 570 930 440 1065 505 1155 545 1270 600
 N/A
N/A 840 395 1020 480 1055 495 830 390 950 450 1010 475 1105 520
ADJUST"
Switch
Positions
First Stage HEAT" Speed First Stage COOL" Speed
1 2 3 4 1 2 3 4
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+
820 385 930 440 1160 550 1210 570 730 345 815 385 865 410 935 440
NORM 760 360 865 410 1045 495 1090 515 680 320 755 355 795 375 855 405
N/A N/A 775 365 930 440 965 455 625 295 695 330 730 345 775 365
N/A − First and second stage HEAT positions shown cannot be used on this model.
NOTES − The effect of static pressure is included in air volumes shown.
First stage HEAT is approximately 91% of the same second stage
 HEAT speed position.
First stage COOL (two−stage air conditioning units only) is approximately 70% of the same second stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position − minimum 500 cfm (235 L/s).