EasyManuals Logo

Lennox Harmony III Installation Instructions

Lennox Harmony III
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #15 background imageLoading...
Page #15 background image
GENERAL
Page 15
HARMONY IIIT ZONE CONTROL SYSTEM
System Flow Diagrams
Shutdown
compressor
stage 1 or 2
Continuous air
delivered to
calling zones
Discharge
air 7°F or more
above cooling
staging jumper
setting
?
4−minute
minimum runtime
in 1st stage
completed
?
5 minutes
since completion
of last cooling
demand
?
Shutdown compres-
sor stages 1 and 2
and blower fan
Ye s
No
Ye s
No
Ye s
No
No
Ye s
No
Ye s
No
Ye s
No
Ye s
No
COOLING
OPERATION
AC/HP
Discharge
air lower than
45°F
?
Monitor
discharge air
temperature
COOLING
DEMAND
RECEIVED
Discharge
air lower than
45°F
?
Energize stage 2
compressor and
ramp indoor
blower to
CFM setting
Energize stage 1
compressor and
ramp indoor
blower to
CFM setting
Monitor
discharge air
temperature
Discharge
air rises above
55°F
?
Cooling
demand
satisfied
?
Cooling
demand
satisfied
?
Discharge
air below cooling
staging jumper
setting
?
De−energize
stage 2
4−minute
minimum runtime
in 2nd stage
completed
?
Ye s
No
No
Ye s
Ye s
Shutdown all
stages com-
pressor /
electric heat
Continuous air
delivered to
calling zones
Discharge
air below heating
staging jumper
setting
?
4−minute
minimum
stage runtime
completed
?
5 minutes
since completion
of last heating
demand
?
Ye s
No
Ye s
No
No
Ye s
No
Ye s
No
Ye s
No
Ye s
No
HEATING
OPERATION
HP & Electric
Heat Strips
Discharge
air higher than
135°F
?
Monitor
discharge air
temperature
HEATING
DEMAND
RECEIVED
Discharge
air higher than
135°F
?
Energize heat strip
stage (W1/W2) and
ramp indoor blower to
CFM setting
Energize (Y1/Y2)
compressor heat
stage and ramp
indoor blower to
CFM setting
Monitor
discharge air
temperature
Discharge
air falls below
130°F
?
Was 2nd
stage (Y2)
running
?
Heating
demand
satisfied
?
Discharge
air 20°F or more
above heating
staging jumper
setting
?
De−energize
furnace W1 &
W2
2−mininute
minimum
stage runtime
completed
?
Ye s
No
No
Ye s
Ye s
Order of Staging:
HP stg 1 (Y1)
HP stg 2 (Y2)
Elec strip stg 1 (W1)
Elec strip stg 2 (W2)
Heating
demand
satisfied
?
No
Upstage
Was 2nd
stage (W2)
running
?
Ye s
Shutdown compres-
sor stages 1 and 2
and blower fan
Ye s
Ye s
No
No
Upstage

Table of Contents

Other manuals for Lennox Harmony III

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox Harmony III and is the answer not in the manual?

Lennox Harmony III Specifications

General IconGeneral
BrandLennox
ModelHarmony III
CategoryControl Systems
LanguageEnglish

Related product manuals