PIAB Calculation Worksheet
Page 60
505023M 08/11
PIAB Calculation Worksheet
PIAB = [(Required CFM − Minimum CFM) / (Maximum CFM − Minimum CFM)] * 100
Sample CFM ' Required Minimum Maximum Minimum
Sample PIAB = ([___920 450 ] / [ 2000 450 ]) x 100
==
bb
Sample PIAB = ([ 470 ] / [ 1550 ]) x 100
=
b
Sample PIAB = [ 0.303 ] x 100 = 30 %
Zone 1 CFM ' Required Minimum Maximum Minimum
ZONE 1 PIAB = ([ ] / [ ]) x 100
==
bb
ZONE 1 PIAB = ([ ] / [ ]) x 100
=
b
ZONE 1 PIAB = [ ] x 100 = %
Zone 2 CFM ' Required Minimum Maximum Minimum
ZONE 2 PIAB = ([ ] / [ ]) x 100
==
bb
ZONE 2 PIAB = ([ ] / [ ]) x 100
=
b
ZONE 2 PIAB = [ ] x 100 = %
Zone 3 CFM ' Required Minimum Maximum Minimum
ZONE 3 PIAB = ([ ] / [ ]) x 100
==
bb
ZONE 3 PIAB = ([ ] / [ ]) x 100
=
b
ZONE 3 PIAB = [ ] x 100 = %
Zone 4 CFM ' Required Minimum Maximum Minimum
ZONE 4 PIAB = ([ ] / [ ]) x 100
==
bb
ZONE 4 PIAB = ([ ] / [ ]) x 100
=
b
ZONE 4 PIAB = ( ) x 100 = %