© 1997 Lennox Industries Inc.
Litho U.S.A.
Corp. 9709−L5
Revised 5−2000
HP29
Service Literature
HP29 SERIES UNITS
The HP29 is a residential split-system heat pump. Outdoor coil
size, circuiting and air volume result in a minimum SEER rating
of 10.0. All HP29 units are designed for use with thermal
expansion valves.
Some HP29 units (−211 through −650, −018 and −024) utilize a
reciprocating compressor. These models are furnished with
crankcase heaters. The heater prevents liquid from
accumulating in the compressor. All compressors are
hermetically sealed for trouble-free operation and long service
life. Reciprocating compressor components are
spring-mounted within the sealed housing. A built-in limit
protects the compressor from excessive current and
temperatures. Other HP29 units (−030 through −060) utilize a
scroll compressor. The scroll operates like a standard
heatpump, but is unique in the way that it compresses
refrigerant.
This manual is divided into sections which discuss major
components, refrigerant system, charging procedures,
maintenance, and operation sequence .
All specifications in this manual are subject to change.
SPECIFICATIONS
Model No. HP29-211 HP29-261 HP29-311
Ntf ft(
2
)
Outer coil 11.41 (1.06) 11.41 (1.06) 13.31 (1.24)
Outdoor
Net face area - sq. ft. (m
2
)
Inner coil - - - - - - - - - - - -
Outdoor
Coil
Tube diameter in. (mm) & no. of rows 5/16 (7.9)  1 5/16 (7.9)  1 5/16 (7.9)  1
Coil
Fins per inch (m) 22 (866) 22 (866) 22 (866)
Diameter  in. (mm) & no. of blades 18 (457)  3 18 (457)  3 18 (457)  4
Outdoor
Motor hp (W) 1/6 (124) 1/6 (124) 1/6 (124)
Outdoor
Coil
F
Cfm (L/s) 2400 (1135) 2400 (1135) 2500 (1180)
Coil
Fan
Rpm 1105 1105 1100
Watts 180 180 200
*Refrigerant charge furnished (HCFC-22) 4 lbs. 5 oz. (1.96 kg) 4 lbs. 4 oz. (1.92 kg) 4 lbs. 15 oz. (2.24 kg)
Liquid line  in. (mm) o.d. connection (sweat) **3/8 to 5/16 (8) **3/8 to 5/16 (8) **3/8 to 5/16 (8)
Vapor line  in. (mm) o.d. connection (sweat) 5/8 (15.9) 5/8 (15.9) 3/4 (19.1)
Shipping weight  lbs. (kg) 1 package 152 (69) 152 (69) 164 (74)
*Refrigerant charge sufficient for 20 ft. (6.1 m) length of refrigerant lines.
**5/16 to 3/8 reducer coupling supplied with unit.
SPECIFICATIONS
Model No. HP29-411/HP29-41 HP29-461/HP29-463 HP29-511/HP29-513 HP29-651/HP29-653
Net face area sq ft (m
2
)
Outer coil 15.21 (1.41) 15.21 (1.41) 15.21 (1.41) 15.21 (1.41)
Outdoor
Net face area - sq. ft. (m
2
)
Inner coil - - - - 5.44 (0.51) 5.44 (0.51) 14.50 (13.5)
Outdoor
Coil
Tube diameter in. (mm) & no. of rows 5/16 (7.9)  1 5/16 (7.9)  1.37 5/16 (7.9)  1.37 5/16 (7.9)  2
Fins per inch (m) 22 (866) 22 (866) 22 (866) 22 (866)
Diameter  in. (mm) & no. of blades 18 (457)  4 18 (457)  4 18 (457)  4 18 (457)  4
Outdoor
Motor hp (W) 1/6 (124) 1/6 (124) 1/3 (249) 1/3 (249)
Outdoor
Coil
F
Cfm (L/s) 2520 (1190) 2500 (1180) 2950 (1390) 2930 (1385)
Coil
Fan
Rpm 1100 1100 1100 1100
Watts 200 200 310 310
*Refrigerant charge furnished (HCFC-22) 6 lbs. 3 oz. (2.81 kg) 7 lbs. 13 oz. (3.54 kg) 7 lbs. 1 oz. (3.20 kg) 9 lbs. 0 oz. (4.08 kg)
Liquid line  in. (mm) o.d. connection (sweat) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5)
Vapor line  in. (mm) o.d. connection (sweat) 3/4 (19.1) 7/8 (22.2) 7/8 (22.2) 1-1/8 (28.6)
Shipping weight  lbs. (kg) 1 package 174 (79) 199 (90) 206 (93) 221 (100)
*Refrigerant charge sufficient for 20 ft. (6.1 m) length of refrigerant lines.
Библиотека СОК
Question and Answer IconNeed help?

Do you have a question about the Lennox HP29-511 and is the answer not in the manual?

Lennox HP29-511 Specifications

General IconGeneral
BrandLennox
ModelHP29-511
CategoryHeat Pump
LanguageEnglish

Summary

HP29 Unit Information and Components

Defrost System Operation (Pre-April 2002)

Defrost System Components and ESD Precautions

Details defrost thermostat, control, and ESD precautions for early HP29 units.

Defrost Thermostat and Control Board Functions

Explains the operation of the defrost thermostat S6 and CMC1 control board.

Defrost System Operation (April 2002 and Later)

Updated Defrost Thermostat and Control

Covers defrost thermostat and control board for HP29 units built from April 2002 onwards.

Defrost Control Timing Pin Adjustments

Explains how to set defrost intervals using timing pins on the control board.

Compressor Types and Specifications

Reciprocating Compressor Specifications

Provides detailed specifications for reciprocating compressors used in HP29 series units.

Scroll Compressor Description and Operation

Details the scroll compressor concept, operation, and potential issues like deep vacuum.

Refrigerant System Components

Refrigerant Line Service Valve Operation

System Charging Procedures

Expansion Valve System Charging Methods

Wiring Diagrams and Operation Sequences

Single-Phase Wiring Diagrams

Illustrates wiring for single-phase HP29 units with reciprocating and scroll compressors.

Three-Phase Wiring Diagrams

Shows wiring for three-phase HP29 units with reciprocating and scroll compressors.

Single-Phase Operating Sequence

Details the sequence of operation for single-phase HP29 units in cooling, heating, and defrost modes.

Three-Phase Operating Sequence

Outlines the sequence of operation for three-phase HP29 units.