Page 18
TABLE 5
Normal Operating Pressures
Outdoor Coil
Entering Air
Temperature
HP29−090−2*
Discharge
+
10 psig
HP29−090−2*
Vapor
+
5 psig
HP29−120−2**
Discharge
+
10 psig
HP29−120−2**
Vapor
+
5 psig
65_F (18_C) 188 69 180 64
75_F (24_C) 216 71 206 66
85_F (29_C) 248 72 236 67
95_F (35_C) 283 74 269 69
105_F (41_C) 319 76 304 70
115_F (46_C) 360 78 345 72
* HP29−090 tested with CB17/CBH17−95V. **HP29−120 tested with CB17/CBH17−135V.
TABLE 6
NORMAL OPERATING PRESSURES
Outdoor Coil
Entering Air
Temperature
HP29−090−3*
Discharge
+
10 psig
HP29−090−3*
Vapor
+
5 psig
HP29−120−3**
Discharge
+
10 psig
HP29−120−3**
Vapor
+
5 psig
65°F (18°C) 175 66 180 64
75°F (24°C) 202 69 206 66
85°F (29°C) 232 71 236 67
95°F (35°C) 263 72 269 69
105°F (41°C) 298 74 304 70
115°F (46°C) 336 76 345 72
* HP29−090 tested with CB17/CBH17−95V. **HP29−120 tested with CB17/CBH17−135V.