INNOV@ ECFAN DHR -AGU-0912-E • 29 •
MODELS
DHADR
DHAUR
0532 0592 0602 0692 0762
Power supply V/Ph/Hz
400V / 3Ph + N + PE / 50Hz
Air flow
m
3
/h
14150 19415
COMPRESSOR
Type
-
Scroll
Cooling capacity (24C; 50% RH; external air T
35C)
kW
53.94 59.08 64.44 71.03 78.59
Power consumption
kW
13.94 16.72 16.14 19.53 22.10
Nominal current
A
26.44 31.48 30.76 35.37 39.00
FLA
A
20 29 32
LRA
A
130 135
Oil charge
l
3.25 3.30 3.25
FINNED EVAPORATOR COIL
Front surface
m
2
1.5 1.9
Geometry
-
25 x 22
Rows
Nr.
4
Type of fins
Type
Hydrophilic
Fin pitch
mm
2.1
SHR
-
0.84 0.80 0.90 0.85 0.81
FAN SECTION
Type of fans
-
Radial - EC
Power supply
V/Ph/Hz
400V / 3Ph / 50Hz
Fans
Nr.
3
Current consumption
A
4.36 4.93
Power consumption
W
2718 3074
AESP
Pa
30
AESP (max. fan speed)
Pa
274.2 363.0
FILTER SECTION
Filter efficiency
-
G4
Overall surface
m
2
4.49
Fire resistance class
-
1
ELECTRICAL HEATERS
Total heating capacity
kW
9.6 12.8
Heaters
Nr.
6 8
Material
-
Aluminium
HOT GAS REHEATING COIL
Heating capacity
kW
- - 51.30 52.70 53.90
Front surface
m
2
1.5 1.9
HOT WATER REHEATING COIL
Heating capacity (water 45/40C)
kW
33.8 34.5 52.32 51.5 53.7
Front surface
m
2
1.1 1.7
Water flow
m
3
/h
5879 5995 9091 8957 9332
Water side pressure drop
kPa
41.8 43.2 35.7 34.8 37.4
Valve pressure drop
kPa
13.5 14 32.2 31.3 34
HUMIDIFIER
Capacity
kg/h
8
Power consumption
kW
6
DIMENSIONS
Height x Lenght x Depth
mm
1998 x 2020 x 795 1998 x 2510 x 795
Unit weight
kg
730 745 940 958 979