INNOV@ ECFAN DHR -AGU-0912-E 33
MODELS
DHZDR
DHZUR
0532 0592 0602 0692 0762
Power supply V/Ph/Hz
400V / 3Ph + N + PE / 50Hz
Air flow
m
3
/h
14150 19415
WATER TEMPERATURE 15C / 30C
Cooling capacity
kW
59.84 66.19 71.23 79.82 87.59
Power consumption
kW
10.92 12.76 12.82 14.86 16.88
Waterflow
[l/h]
3950 4400 4607 5223 5853
Pressure drop
[kPa]
10.5 12.6 13.7 10.5 12.8
COMPRESSOR
Type
-
Scroll
Nominal current
V/Ph/Hz
400V / 3Ph / 50Hz
Nominal current
A
11.48 13.43 13.45 16.37 16.35
FLA
A
20 29 32
LRA
A
130 135
Oil charge
l
3.25 3.30 3.25
FINNED EVAPORATOR COIL
Front surface
m
2
1.5 1.9
Geometry
-
25 x 22
Rows
Nr.
4
Type of fins
Type
Hydrophilic
Fin pitch
mm
2.1
SHR
-
0.79 0.76 0.85 0.80 0.76
FAN SECTION
Type of fans
Tipo
Radial - EC
Fans
Nr.
2 3
Current consumption
A
3.98 4.41
Power consumption
W
2718 3074
AESP
Pa
30
AESP (max. fan speed)
Pa
274.2 363.0
FILTER SECTION
Filter efficiency
-
G4
Overall surface
m
2
4.49
Fire resistance class
-
1
ELECTRICAL HEATERS
Total heating capacity
kW
9.6 12.8
Heaters
Nr.
6 8
Material
-
Aluminium
HOT GAS REHEATING COIL
Heating capacity
kW
38.60 - 51.30 52.70 53.90
Front surface
m
2
1.5 1.9
HOT WATER REHEATING COIL
Heating capacity (water 45/40C)
kW
31.30 - 44.30 46.00 47.60
Front surface
m
2
1.5 1.9
Water flow
m
3
/h
5.384 - 7.620 7.912 8.187
Water side pressure drop
kPa
45.00 - 34.00 35.00 39.00
Valve pressure drop
kPa
29.00 - 27.00
HUMIDIFIER
Capacity
kg/h
8
Power consumption
kW
6
DIMENSIONS
Height x Lenght x Depth
mm
1998 x 2020 x 795 1998 x 2510 x 795
Unit weight
kg
730 745 940 958 979